1 self test of the display, 2 calibrating the touch screen, Self test of the display – Beijer Electronics iX Panel TA100 EN User Manual

Page 23: Calibrating the touch screen

Advertising
background image

Hardware Replacement

5. Remove the mounting plate (9 torx screws). Gently lift the mounting plate

with the display and power card.

9 x torx screws

6. Flip the mounting plate and unscrew the 4 torx screws.

4 x torx screws

7. Re-assemble the panel in reverse order.

7.4.1

Self Test of the Display

To perform a self test of the display, follow the steps below:
1. Start the operator panel in a self test mode (see table in the

Mode Switches

sec-

tion).

2. Go to the display test, by running or skipping the preceding tests. Verify that

the display works.

3. If the screen does not work, try fault tracing, see the

Fault Tracing

section.

7.4.2

Calibrating the Touch Screen

Follow the steps below to calibrate the touch screen:
1. Set the MODE switches to the correct positions in order to enter the Service

Menu mode (see table in the

Mode Switches

section).

2. Switch on the power and follow the instructions.
3. Power off the operating panel.
4. Reset all MODE switches to the OFF position.

Beijer Electronics, MAEN013A

23