APPLICATION NOTE AN-BEI-P2-050

Date: 15/02/12

AN-BEI-P2-050 Open Loop Permanent Magnet Motor Control

3

Firmware Overview – Standard Parameters for PM motor set-up:

The following parameters are taken from the main Beijer Frequency Inverter P2 user manual but are required for
set-up / configuration of a PM motor. Parameters highlighted in ‘Blue’ are essential for successful PM motor control
with the Beijer Frequency Inverter P2. They are not configured during the auto-tune function and must be entered
manually:-

Par.

Description

Range

Units

Default

Explanation

P1-03

Acceleration
ramp time

0 – 3000.0

Sec

5.0

Acceleration ramp time from 0 to base speed (P1-09) in
seconds

P1-04

Deceleration
ramp time

0 – 3000.0

Sec

5.0

Deceleration ramp time from base speed (P1-09) to
standstill in seconds

P1-07

Nominal back
emf

0 – 250 / 500

Volts

(rms)

8

Phase – Phase voltage imposed by magnets while
motor rotating at motor rated speed (P1-10)

P1-08

Motor rated
current

25 – 100% of drive
rated current

Amps

(rms)

0.13

Rated (nominal) phase current of the motor (used for
over-current protection)

P1-09

Motor rated
frequency

25 – 500

Hz

0.13

Rated (nominal) frequency of the motor.

P1-10

Motor rated
speed

0 – 60,000

Rpm

0

Rated (nominal) speed of the motor.

P2-24

Switching
frequency

4 - 32

kHz

Model

Based

Value

Effective Power Stage switching frequency. Higher
frequencies give smoother operation but care must be
taken to apply necessary de-rate factors.

P4-02

Motor
parameter
auto-tune

0: Disable
1: Enable

---

0

When set to 1 the drive will perform an auto-tune
immediately of exiting the parameter. Values will be
written automatically to parameters P7-01, P7-03, &
P7-06.

P4-03

Speed
Controller
proportional
Gain

0.0 – 400.0

%

25.0

Sets the proportional gain value for the speed
controller. Higher values provide better output
frequency regulation and response. Too high a
value can cause instability or even over current
trips. For applications requiring best possible
performance, the value should be adjusted to suit
the connected load.

P4-04

Speed
Controller
integral time
constant

0.000 – 1.000

s

0.500

Sets the integral time for the speed controller.
Smaller values provide a faster response in
reaction to motor load changes, at the risk of
introducing instability. For best dynamic
performance, the value should be adjusted to suit
the connected load.

P4-07

Maximum
motoring
Torque limit

P4-08 – 200

%

200

When P4-01 is set to 3, sets the maximum torque limit.

P4-09

Maximum
generating
Torque limit

0.0 - 200

%

200

Sets the maximum regenerating torque limit permitted
by the drive.