APPLICATION NOTE AN-BEI-P2-050

Date: 15/02/12

AN-BEI-P2-050 Open Loop Permanent Magnet Motor Control

8

Permanent magnet motors quick set-up:

The quick start is intended as a basic first step to successfully running the motor. For Optimum performance the
full programming and optimisation procedure should be followed.

Quick Step 1: Setting of the required parameters

Set the following parameters in the sequence they are listed.

P1-07: Nominal back emf (rms Phase-Phase)

-

= Motor Dependant

P1-08: Motor rated current (rms Phase) -

-

= Motor Dependant

P1-09: Motor rated frequency (Hz)

-

-

= Motor Dependant

P1-10: Motor rated speed (rpm) -

-

-

= Motor Dependant

P1-14: Parameter access code -

-

-

= 201

P2-24: Switching frequency (kHz)

-

-

= 16

P4-01: Control Mode

-

-

-

-

= 3

P4-03: Speed Controller proportional Gain (%) -

= 50

P4-04: Speed Controller integral time constant (ms)

= 100

Quick Step 2: Complete Auto-tune function

Note: Safe Torque Off input (terminal 12 and 13) needs to be connected in order to enable the safe torque off
function and allow auto-tune and motor control. See connection diagram below.

Set the following parameter. Drive will perform auto-tune on exit of parameter entry.

P4-02: Auto-tune Function

-

-

= 1

Wait for completion of auto-tune.

Quick Step 3: Check motor operation

Apply enable and speed set-point inputs to the Beijer
Frequency Inverter P2 P-2 Default configuration is shown right.

Vary speed set-point and check smooth operation of the motor.


Optional:

To set Beijer Frequency Inverter P2 in keypad mode set
parameter P12 = 1 Beijer Frequency Inverter P2 can now be
controlled direct from the keypad.

Quick Step 4: Set Current magnetising time

Set the following parameter to adjust Current magnetising time.

P7-12: Current magnetising time

Adjust upward if the rotor cannot be seen to orientate on start

up.

Adjust downward if a significant delay follows the orientation
of the rotor on start up.

Quick Step 5: Set Low speed boost parameters

Check low speed operation of the motor. If torque performance
at low speed needs adjustment set the following values.

P7-14: Boost Current Level

-

-

= 25%

P7-14: Boost Frequency

-

-

= 10%

Values should be optimised following on from the quick start procedure.

1

2

3

4

5

6

7

P1-12 = 0
P1-13 = 1

Input 1:
O: Stop (Disable)
C: Run (Enable)

Input 3:

Enable

Imput 2:

+24V Output

+10V Output

0V

Analog Speed Ref

12

13

Safe Torque Off Input

Safe Torque Off 0V