CANopen USER GUIDE

Beijer Electronics Automation AB

PAGE 7

Object

200Ah : Drive status register

200Ah Drive Status Register

Bit 15 ~ Bit 8

Bit 7,6,5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Trip code if bit 1 is set to 1

N/A

Service

due

Inhibit

Hand

mode

Trip

Run

If bit 0 is set, drive is in run condition.

If bit 1 is set, drive is in trip condition.

If bit 2 is set, drive is in hand control mode (HVAC drive only)

If bit 3 is set, drive is in inhibit mode.

If bit 4 is set, this indicates that drive/system is due to service

Bit 5 to Bit 7 are reserved. (These bits may be used at a later stage)

Bit 8 to Bit 15 provide the error/trip code when drive is in trip condition. (Error code list is not provided here)

Object

200Bh : Motor speed (Hz)

The data value of this object provides the motor speed information in Hz unit. The data includes one decimal

place.

For example, a data value of 500=50.0Hz, -125=-12.5Hz

Object

200Ch : Motor speed (IDL internal format)

The data value of this object provides the motor speed information in IDL internal data format. See object

2004h for more information about this speed format

Object

200Dh : Motor current (A)

The data value of this object provides motor current information. The value contains one decimal place.

For example, if the data value is 30, this means the motor current is 3.0A

Object

200Eh : Motor torque (Q12)

The data value of this object provides motor output torque information. The value is in Q12 format, 4096 =

100%.

Object

200Fh : Motor power (kW)

The data value of this object provides motor output power information. The value contains two decimal places.

For example, 1234=12.34kW

--- END ---