PLC SYSTEM SPECIFICATIONS

2

Power Supply
Voltage / frequency

AC
DC

100 to 240 VAC, 50/60 Hz
24 VDC

Operating
Voltage range

AC
DC

85 to 264 VAC
20.4 to 26.4 VDC

Power
Consumption

AC
DC

60 VA max.
20 W max.

Inrush current

60 A max.

External power supply

Voltage
Output capacity

24 VDC
200 mA

Insulation resistance

20 mega ohms min. at 500
VDC between AC terminals
and ground terminal

Noise resistance

1500 V (peak to peak) with
a pulse width of 0.1 to 1
microsecond 1 nanosec-
ond rise time pulse (tested
with noise simulator)

Dielectric strength

2300 VAC at 50/60 Hz for
one minute with leakage
current of 10 mA max. be-
tween all the external AC
terminals and ground ter-
minal

Vibration resistance

10 to 57 Hz width and am-
plitude of 0.075 mm, and
57 to 150 Hz with an accel-
eration of 9.8 m/s

2

(IG) in

X, Y, and Z directions for
80 minutes each (ie. Swept
for 8 minutes, 10 times)

Shock resistance

147 m/s2 (15 G) in X, Y
and Z directions 3 times
each.

Operating Conditions

Ambient temperature

0 to 55 degrees C (32 to
122 degrees F)

Ambient humidity

10% to 90% (no condensa-
tion)

Ambient environment

With no corrosive gas

Storage conditions

Ambient temperature

-20 to 75 degrees C
(-4 to 165 degrees F)

Power supply holding time

10 ms minimum for AC
models and 2 ms minimum
for DC models