TROUBLESHOOTING

Problem:
No Reading

Check that you have the correct supply
voltage at the power terminal blocks.

Check that wiring configurations and all
DIP switch settings are as in Figures #1,
#2 and #7
.

Verify that the terminal screws are all
connected tightly and that all of the wires
are firmly in place.

Erratic Readings

Verify that all of the wires are terminated
properly.

Make sure that there is no condensation
on the board.

Check that the input power is clean. In
areas of high RF interference or noise,
shielded cable may be necessary to
stabilize signal.

Inaccurate Readings

If you suspect that the transmitter is not
reading within the specified tolerance,
please contact the factory for further
assistance.

4-20m A Output: 250 Ohm Load 22 - 40
VDC / 22 - 28 VAC

RH M easurement Range

0 - 100% RH

4-20m A Output: 500 Ohm Load 24 - 40
VDC / 24 - 28 VAC (500 Ohm Load Max)

RH Accuracy @ 77

o

F (25

o

C)

± 1% over 20% span (between 20 to 90%)
± 2% , 3% , or 5% from 10 to 95%

Repeatability

0.5% RH

Operating Humidity Environment 0 to 95% RH

Supply Current

24mA M ax

Operating Temp. E nvironment

32 to 122

°F (0 to 50°C)

2-Wire, 4-20 mA

Storage Temp. Range

-40 to 160

°F (-40 to 71°C)

3-Wire, 4-20mA

Supply Voltage

RH Output

PRODUCT SPECIFICATIONS