Barksdale BPS3000 User Manual

Page 4

Advertising
background image

7.1 Parameters

Parameter

14-segment display

Description

SP1/SP2*

/

Hysteresis function: Switching point of solid state contact

FH1/FH2*

/

Window function: Window High solid state contact

rP1/rP2*

/

Hysteresis function: Hysteresis of solid state contact

FL1/FL2*

/

Window function: Window Low solid state contact

EF

Extended programming functions

rES

Reset parameters to factory settings

dS1/dS2*

/

Switching time delay – the set contact rating must be
permanently exceeded to trigger a switching function

dr1/dr2*

/

Switching time delay – the contact rating must be
permanently lower than the set contact rating to trigger a
switching function

Switching function of solid state contact

HNO

= Hysteresis function, NO contact

HNC

= Hysteresis function, NC contact

FNO

= Window function, NO contact

FNC

= Window function, NC contact

Ou1/Ou2*

/

DIA

= Diagnostic function, NO contact (only Ou2)

uni

Select unit: bar, PSI, MPa

If the measuring range is outside the display range, unit
selection is impossible. The parameter "uni" is not
displayed.

Analog output

I

= 4... 20 mA

U

= 0... 10 V

I.INV

= 20... 4 mA

OuA**

U.INV

= 10... V

ASP**

Analog start value

Parameter

14-segment display

Description

AEP**

Analog end value

dPA**

Damping of analog output

ErS.A**

Error signal of analog output
Values: < 3.6 or > 22 or Off

Hi

Saved value of highest pressure measured

Lo

Saved value of lowest pressure measured

COF

Offset correction (max. 10 % of measuring range)

ddis

Damping display

Fdis

Rotate display through 180°

LocK

Locking feature

* only models with 2nd switching contact

** only models with analog output

Error list

Parameter

14-segment display

Description

sens

Sensor defect

SC1

Short circuit, solid state contact 1

SC2

Short circuit, solid state contact 2

AOut

Open output, short circuit

OL

Sensor limit positive

UL

Sensor limit negative

KEY

Internal defect

7