4. Programming Menu (continue)

Dialog
item

Value

Function/Description

Inversion of switching output SP1

= high-level-fail-save (normally open function)

= low-level-fail-save (normally closed function)

**

= window technology

= error output

= standard evaluation

0 ... xxx

Switch-on point for SP2; if the ON value is smaller than the OFF value the
switching point evaluation is falling

0 ... xxx

Switch-off point for SP2

0.0 s ... 9.9 s

Switch-on delay for SP2 in seconds

0.0 s ... 9.9 s

Switch-off delay for SP2 in seconds

Inversion of switching output SP2

= high-level-fail-save (normally open function)

= low-level-fail-save (normally closed function)

** Note: When changing units from psi to bar or bar to psi, the switching point values must be changed
accordingly

. For pressure ranges greater than 1000 psi, only the selections of “PSH” and „„bar” are

available. If other units are selected t

he measurement will default to “bar” and switch point settings will

require re-setting.

Programming Menu Continued

Dialog
item

Value

Function/Description

Only models with analog output:

*

0 ... xxx

Scale the analog output - start value (e. g. 0 bar = 4 mA)

*

0 ... xxx

Scale the analog output - end value (e. g. 400 bar = 20 mA)
(output signal start value always corresponds to the display initial value, e. g. 0
bar = 4mA)
Maximum turn-down 4 : 1, i.e. at values below 25 % of the measuring range
the analog output is switched off

IMPORTANT

* Flashing of the mean segment signals a negative setting value.

Programming Menu Continued

Dialog
item

Value

Function/Description

0 ... xxx

Display of peak value

“Max” (xxxx: = max. 125 % f. s.)

Delete the maximum value memory

= no deletion

= delete value

Error display:

= no error

= exceeding pos. measuring range

= exceeding neg. measuring range

= sensor error

= error switching output 1

= error switching output 2

= data error (EEProm)

= program error

= calibration error

= error analog out

IMPORTANT

* Flashing of the mean segment signals a negative setting value.