Blower performance data, Wdg air handler series, Installation, operation & maintenance – Comfort-Aire WDG Air Handler Series User Manual

Page 16: Heat controller, llc, Wdg blower

Advertising
background image

16

Installation, Operation & Maintenance

WDG AIR HANDLER SERIES

Heat Controller, LLC

WDG Blower

Blower Performance Data

Airfl ow in CFM with wet coil and clean air fi lter

Model

Max
ESP

(in. wg)

Fan

Motor

(hp)

Tap

Setting

Cooling Mode

Dehumid Mode

Heating Mode

AUX
CFM

Aux/

Emerg

Mode

Stg 1

Stg 2

Fan

Stg 1

Stg 2

Fan

Stg 1

Stg 2

Fan

TAH

026

0.50

1/2

4

810

950

475

630

740

475

920

1060

475

4

1060

0.50

1/2

3

725

850

425

560

660

425

825

950

425

3

950

0.50

1/2

2

620

730

370

490

570

370

710

820

370

2

820

0.50

1/2

1

520

610

300

600

690

300

1

690

TAH

038

0.50

1/2

4

1120

1400

700

870

1090

700

1120

1400

700

4

1400

0.50

1/2

3

1000

1250

630

780

980

630

1000

1250

630

3

1350

0.50

1/2

2

860

1080

540

670

840

540

860

1080

540

2

1350

0.50

1/2

1

730

900

450

730

900

450

1

1350

TAH

049

0.75

1

4

1460

1730

870

1140

1350

870

1560

1850

870

4

1850

0.75

1

3

1300

1550

780

1020

1210

780

1400

1650

780

3

1660

0.75

1

2

1120

1330

670

870

1040

670

1200

1430

670

2

1430

0.75

1

1

940

1120

560

1010

1200

560

1

1350

TAH

064

0.75

1

4

1670

2050

1020

1300

1600

1020

1860

2280

1020

4

2280

0.75

1

3

1500

1825

920

1160

1430

920

1650

2050

920

3

2040

0.75

1

2

1280

1580

790

1000

1230

790

1430

1750

790

2

1750

0.75

1

1

1080

1320

660

1200

1470

660

1

1470

Factory shipped on Tap Setting 2
During Auxiliary operation (residential units only) the CFM will run at the higher if the heating (delay jumper) or AUX settings
Airfl ow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1” fi berglass fi lter
Do not select Dehumidifi cation mode if HP CFM is on setting 1
All units AHRI/ISO/ASHRAE 13256-1 rated HP (Cooling) Delay (Heating) CFM Setting 3

WDG

024

WDG

036

WDG

048

WDG

060