Warning, H. return air – Comfort-Aire TGRG Series for R-410A User Manual

Page 16

Advertising
background image

Place the unit as close to the conditioned space as possible allowing clearances as indi-
cated. Run ducts as directly as possible to supply and return outlets. Use of non-flam-
mable weatherproof flexible connectors on both supply and return connections at unit to
reduce noise transmission is recommended.

On ductwork exposed to outside temperature and humidity, use a minimum of 2” of
insulation and a vapor barrier. Distribution system in attic, furred space or crawl space
should be insulated with at least 2” of insulation.

1

2

” to 1” thick insulation is usually suffi-

cient for ductwork inside the air conditioned space.

Provide balancing dampers for each branch duct in the supply system. Properly support
ductwork from the structure.

IMPORTANT: In the event that the return air ducts must be run through an “unconfined”
space containing other fuel burning equipment, it is imperative that the user/homeowner
must be informed against future changes in construction which might change this to a
“confined space.” Also, caution the user/homeowner against any future installation of
additional equipment (such as power ventilators, clothes dryers, etc., within the existing
unconfined and/or confined space which might create a negative pressure within the
vicinity of other solid, liquid, or gas fueled appliances.

H. RETURN AIR

!

WARNING

NEVER ALLOW PRODUCTS OF COMBUSTION OR THE FLUE PRODUCTS TO
ENTER THE RETURN AIR DUCTWORK, OR THE CIRCULATING AIR SUPPLY.
ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED
TO THE FURNACE WITH SHEET METAL SCREWS, AND JOINTS TAPED. ALL
OTHER DUCT JOINTS MUST BE SECURED WITH APPROVED CONNECTIONS
AND SEALED AIRTIGHT.

FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCU-
LATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS
CONDITIONS, INCLUDING CAROBON MONOXIDE POISONING THAT COULD
RESULT IN PERSONAL INJURY OR DEATH.

FIGURE 13

PITCHED ROOFTOP INSTALLATION, ON ROOFJACK, DOWNFLOW DUCTWORK, ATTIC OR
DROP CEILING DISTRIBUTING SYSTEM. PITCH UNIT TOWARD DRAIN.

16