Vii. gas supply, condensate drain and vii. piping, A. gas connection – Comfort-Aire TGRG Series for R-410A User Manual

Page 19

Advertising
background image

VII. GAS SUPPLY, CONDENSATE DRAIN AND

VII.

PIPING

A. GAS CONNECTION

IMPORTANT: Connect this unit only to gas supplied by a commercial utility.

1. Install gas piping in accordance with local codes and regulations of the local utility

company. In the absence of local codes, the installation must conform to the specifi-
cations of the National Fuel Gas Code, ANSI Z223.1 - latest edition.

NOTE: The use of flexible gas connectors is not permitted.

NOTE: The Commonwealth of Massachusetts requires the gas shut-off valve to be
a T-handle gas cock.

2. Connect the gas line to the gas pipe inlet opening provided into the 1/2” inlet valve.

See Figure 2 for typical piping.

3. Size the gas line to the furnace adequate enough to prevent undue pressure drop

and never less than 1/2”.

4. Install a drip leg or sediment trap in the gas supply line as close to the unit as possi-

ble.

5. Install an outside ground joint union to connect the gas supply to the control assem-

bly at the burner tray.

6. Gas valves have been factory installed. Install a manual gas valve where local codes

specify a shut-off valve outside the unit casing. (See Figure 19.)

7. Make sure piping is tight. A pipe compound resistant to the action of liquefied

petroleum gases must be used at all threaded pipe connections.

8. IMPORTANT: Any additions, changes or conversions required for the furnace to sat-

isfactorily meet the application should be made by a qualified installer, service
agency or the gas supplier, using factory-specified or approved parts. In the com-
monwealth of Massachusetts, installation must be performed by a licensed plumber
or gas fitter for appropriate fuel.

IMPORTANT: Disconnect the furnace and its individual shutoff valve from the gas sup-
ply piping during any pressure testing of that system at test pressures in excess of 1/2
psig or isolate the system from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of this gas supply system at pressures
equal to or less than 1/2 PSIG.

FIGURE 19

SUGGESTED GAS PIPING

FROM GAS
METER

*

Factory supplied grommet must be utilized.

MANUAL GAS
SHUT-OFF
VALVE

UNIT GAS SUPPLY
CONNECTION

*

ROOF OR GROUND LEVEL INSTALLATION

Nominal

Iron Pipe

Size,

Inches

Equivalent Length of Pipe, Feet

10

20

30

40

50

60

70

80

1

/

2

132

92

73

63

56

50

46

43

3

/

4

278

190

152

130

115

105

96

90

1

520

350

285

245

215

195

180

170

1

1

/

4

1,050

730

590

500

440

400

370

350

1

1

/

2

1,600 1,100

890

760

670

610

560

530

TABLE 1

GAS PIPE CAPACITY TABLE (CU. FT./HR.)

FIGURE 19

SUGGESTED GAS PIPING

19

Advertising