Aprilaire 8100 User Manual

Safety and installation manual, Model 8100, Energy recovery ventilators

Advertising
background image

• Provides year-round fresh air

• Recovers 77% of the apparent heating or cooling energy from the exhausted air

SAFETY AND INSTALLATION MANUAL

ENERGY RECOVERY VENTILATORS

®

MODEL 8100

See Warnings – Page 3

–16–

DIAGRAM SHOWING POSITION OF AIR FLOW

MEASURING DEVICES AND BALANCING DAMPERS

Form No. 3028

2.5.08.01

Printed in U.S.A.

DP10002582

FIGURE 11

DAMPER

DAMPER

PRESSURE GAUGES

AIR FLOW

MEASURING DEVICE

(RESEARCH PRODUCTS

#5158)

AIR FLOW

MEASURING DEVICE

(RESEARCH PRODUCTS

#5158)

STALE AIR

FROM HOUSE

FRESH AIR

FROM

OUTSIDE

(DAMPERED

DUCT)

(INSULATED

DUCT)

STALE AIR TO

OUTSIDE

FRESH AIR

TO HOUSE

(DAMPERED

DUCT)

(INSULATED DUCT)

*

A sound absorber at least 6' long consisting of 1" thick

rigid fiberglass duct or insulated flexible duct (ATCO
series 70 or equivalent) is recommended for maximum
absorbing of air movement sounds between the unit and
the living space return grille.

NOTE: Dampers, air flow measuring devices and pressure

gauges not included.

5' MINIMUM

STRAIGHT

SECTION

5' MINIMUM

STRAIGHT

SECTION

Airflow in a 6" duct as measured using

RP Airflow Measuring Device #5158

Gauge

Gauge

Readings

Airflow

Readings

Airflow

(in. w.g.)

(cfm)

(in. w.g.)

(cfm)

0.005

30

0.065

119

0.010

44

0.070

124

0.015

55

0.075

128

0.020

64

0.080

132

0.025

72

0.085

137

0.030

80

0.090

141

0.035

86

0.095

145

0.040

93

0.100

149

0.045

98

0.105

152

0.050

104

0.110

156

0.055

109

0.115

160

0.060

114

0.120

163