American Dryer Corp. Super AD-30 User Manual

Page 34

Advertising
background image

30

3. Steam Damper Air System Connections

The pneumatic (piston) damper system requires a clean, dry, regulated external supply of compressed air.
The air connection is made to the system solenoid valve which is located on the rear electric service box.

2) Air Connection

Air connection to system --- 1/8" N.P.T.

3) Air Regulation

No air regulation is provided with the dryer. External regulation of 80 psi must be provided. It is
suggested that a regulator / filter gauge arrangement be added to the compresses air line just before
the dryer connection. This is necessary to insure that correct and clean air pressure is achieved.

3. Steam Damper System Operation

The steam damper, as shown in the illustration below, allows the coil to stay constantly charged eliminating
repeated expansion and contraction. When the damper is opened, the air immediately passes through the
already hot coil, providing instant heat to start the drying process. When the damper is closed, ambient air is
drawn directly into the basket (tumbler), allowing a rapid cool down.

1) Air Requirements

There is no air requirement for dryers with the electromechanical damper option.

C

OMPRESSED

A

IR

S

UPPLY

A

IR

P

RESSURE

Normal

80 psi

Minimum Supply

70 psi

Maximum Supply

90 psi