Optimum protection ld1 – Aico Ei168RC User Manual

Page 6

Advertising
background image

for dwellings where occupants may be at high risk (e.g. elderly)

OPTIMUM PROTECTION

LD1

Optimum Protection LD1: As LD2, but in addition
Smoke or Heat Alarms should be located in all rooms
and other areas of the dwelling.
(apart from toilets or bathroom)

Multi Storey Dwelling LD1

Heat Alarms located in:

(Heat Alarms must be within 5.3m of potential fire
sources)

each Kitchen
garages

Living
Room

Bedroom

Bathroom

Kitchen

Bedroom

Shower

Garage

Smoke or Heat Alarms located in:

each Living room (i.e. most frequently used
daytime room)

Smoke Alarms located:

on each storey
every 7.5 m of hallways and escape routes
within 3m of all bedroom doors
in all other rooms & areas other than listed below

(apart from toilets & bathrooms )

Bedroom

Bedroom

Bedroom

Kitchen / Dining Room

Living Room

Bathroom

Single Storey Dwelling LD1

Heat Alarm

do not fit alarm

Ionisation or Optical
Smoke Alarm

Optical Smoke Alarm

7

B16008-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 6