Aprilaire 8336 User Manual

Page 7

Advertising
background image

7

To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS
VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE
THE THERMOSTAT AND VOID YOUR WARRANTY.

CAUTION: Do not switch system to cool if the temperature is below 50°F (10°C).
This can damage the air conditioning system and cause personal injury.

1. Place the COOL-OFF-HEAT-EM

switch into the COOL position

2. Press the

button until the

temperature setting is at least
3 degrees below the room
temperature. The air conditioning
system should turn on within
a few seconds.

NOTE: When in the COOL mode (or HEAT for single stage heat pumps),
once the thermostat turns off, a built in 5-minute delay prevents the
system from turning on again. This protects the compressor. No
additional time delay relay is required.

3. Put the COOL-OFF-HEAT-EM switch

into the OFF position. The air
conditioning system should turn off.

4. Put the COOL-OFF-HEAT-EM switch

into the HEAT position.

5. Press the

button until the

temperature setting is at least
3 degrees above room temperature.
The heating system should turn on.
The fan may not turn on immediately,
depending upon the fan delay built
into the furnace.

6. Put the COOL-OFF-HEAT-EM switch

into the OFF position. The heating
system should turn off. The fan may
continue to run for a short period
of time.

7. Put the FAN: AUTO-ON switch to the

ON position. The blower fan should
turn on.

8. Put the FAN: AUTO-ON switch to

the AUTO position. The blower fan
should turn off.

COOL-OFF-HEAT-EM

COOL-OFF-HEAT-EM

COOL-OFF-HEAT-EM

>

FAN: AUTO - ON

>

COOL-OFF-HEAT-EM

FAN: AUTO - ON