Wiring guidelines, Preparing captive wires, Video output connector – AMX AV2SM User Manual

Page 8

Advertising
background image

Installation

4

AV2SM A/V Switcher

Wiring Guidelines

The maximum wiring distance between the Central Controller and the AV2SM is determined by

power consumption, supplied voltage, and the wire gauge used for the cable. The maximum wiring

lengths for using AXlink power are based on a minimum of 13.5 volts available at the Central

Controller’s power supply. The maximum lengths allowable between the AV2SM and the Central

Controller are as follows:

Preparing captive wires

1.

Strip 0.25 inch of wire insulation off all wires.

2.

Insert each wire into the appropriate opening on the connector according to the wiring

diagrams and connector types described in this section.

3.

Tighten the screws to secure the wire in the connector. Do not tighten the screws excessively;

doing so may strip the threads and damage the connector.

Video output connector

Connect your output display monitor to the VIDEO connector on the front panel using FIG. 4.

Wiring Guidelines

Wiring size Maximum wiring length

18

1805.7 ft (550.37 m)

20

1142.4 ft (382.20 m)

22

712.2 ft (217.07 m)

24

448.9 ft (136.82 m)

FIG. 4 VIDEO OUTPUT wiring diagram

Output

display

monitor

connector
(female)

AV2SM video

output

connector

(female)

Video Cable

BNC connectors (male)