Specifications

1400 VA

2200 VA

3000 VA

5000 VA

Acceptable input voltage

0 - 325 VAC

Input voltage (on-line operation)*

160 - 253 VAC

208 volt output range*

177 - 229 VAC

120 volt output range *

with 400 VA load
with no load

95 - 130 VAC

100 - 135 VAC

Nominal input frequency

50 or 60 Hz, autosensing

Input protection

Resettable circuit breaker

Frequency limits (on-line operation)

47 to 63 Hz

Transfer time

2 ms typical, 4.5 ms maximum

Maximum load, total

1400 VA/950 W

2200 VA/1600 W

3000 VA/2250 W

5000 VA/3750 W

Maximum load, 120V auxiliary

400 VA/400 W

On-battery output voltage

208 VAC

On-battery frequency

50 or 60 Hz, 0.1 Hz;

unless synchronized to utility during brownout

On-battery waveshape

Low-distortion sine wave

Overload protection (on-battery)

Overcurrent and short-circuit protected, latching shutdown on overload

Overload protection (on-line)

2 pole, 20 Amp UL certified input circuit breaker

Overload protection
(120 VAC auxiliary)

Transformer and output protected by resettable

thermal circuit breaker (on-line and on-battery)

Surge energy rating
(one time, 10/1000

æs waveform)

1120 J

Surge current capability
(one time, 8/20

æs waveform)

6500 A maximum

Surge response time

0 ns (instantaneous) normal mode;

z5 ns common mode

Surge voltage let-through
(percentage of applied ANSI C62.41 Cat. A

6 kV test waveform)

0.30%

Noise filter

Normal and common mode EMI/RFI suppression,

100 kHz to 10 MHz

Battery type

Spill proof, maintenance free, sealed lead-acid

Typical battery life

3 to 6 years, depending on number of discharge cycles

and ambient temperature

Typical recharge time

2 to 5 hours from total discharge

Operating temperature

0 to 40

ΓC (+32 to +104ΓF)

Storage temperature

-15 to +45

ΓC (+5 to +113ΓF)

Operating and storage relative humidity

5 to 95%, non-condensing

Operating elevation

0 to +3,000 m (0 to +10,000 ft.)

Storage elevation

0 to +15,000 m (0 to +50,000 ft.)

Electromagnetic immunity

IEC 801-2 level IV, 801-3 level III, 801-4 level IV

Audible noise in dBA at 1 m (3 ft.)

z55

Safety approvals

Listed to UL 1778, certified to CSA 107.1

EMI verification

FCC/DOC Class A verified

5U Units

RM Units

Size (W x H x D)

43.2

x 19.6 x 54.6 cm

(17.0 x 8.7 x 21.5 in.)

43.2

x 19.6 x 62.2 cm

(17.0 x 8.7 x 24.5 in.)

Weight - net (shipping)

120 (143) lb.

54.3 (64.8) kg

137 (160) lb.

62.0 (72.5) kg

137 (160) lb.

62.0 (72.5) kg

225 (245) lb.
102 (111) kg

3U Units

Tower Units

Size (W x H x D)

43.2 x 13.3 x 62.2 cm

(17.0 x 5.25 x 24.5 in.)

19.6 x 43.2 x 62.2 cm
(8.7 x 17.5 x 26.0 in.)

Weight - net (shipping)

128 (148) lb.

58 (67) kg

230 (250) lb.
105 (114) kg