Appendix A: XL Information

When used with external battery packs, the extended run (XL) UPS offers longer run times than a standard UPS and extra
load protection during battery replacement. When replacing the batteries either in the UPS or battery pack(s), the UPS can
still respond to a power disturbance using the remaining connected batteries. Please refer to the main sections of this
User’s Manual for basic information about the UPS. This appendix provides additional information needed to use
extended run versions of the UPS.

XL Installation

This figure shows the location of the battery pack connector on the 5U SU1400RMXL (top), the
SU3000 tower unit (right), the 5U SU3000RM (bottom), and the SU1000XL tower unit (left).
Some UPS models have the battery pack connector in different positions, but the size and shape
of the connector is always the same.

Battery pack connectors are color coded as shown in the table below. Battery pack connectors are
also keyed to prevent improper connection. Do not try to install battery packs with connectors
that are a different color from the battery pack connector in the UPS.

This UPS

Voltage

Uses this Battery Pack (connector color)

Maximum Number of Battery Packs

SU700XL

SU1000XL

24 VDC

SU24XLBP (gray)

10

SU1400XLT

SU2200XL

SU2200XLT

48 VDC

SU48XLBP (blue)

10

SU3000

SU3000T

SU3000RM

48 VDC

SU48BP (red)

1

SU1400RMXL

SU1400RMXLT

SU2200RMXL

SU2200RMXLT

48 VDC

SU48RMXLBP(blue)

5

Install up to the maximum number of battery packs per XL model UPS following the instructions below.
Note: The 3000 VA UPS accepts only one battery pack.

1. Prepare the UPS to connect the battery

pack(s). Note the holes used to attach the
battery pack connector clamp (near the
center of the connector opening). Use a
#2 Phillips head screwdriver to remove
the battery pack connector clamp from the
back of the UPS.

3. Holding the clamp aside, insert the

battery pack connector into the UPS.

2. Turn the clamp over and loosely attach

one end at the edge of the connector
opening in the UPS.

4. Secure the connector clamp.

Correctly completed XL installation
with two battery packs.

For additional battery packs, repeat this procedure using the battery pack

connectors on the battery packs.

Caution: Do not stack battery packs. Stacking results in a tipping hazard.