Bryant DURAPAC 580F User Manual

Page 43

Advertising
background image

43

TROUBLESHOOTING

I. UNIT TROUBLESHOOTING

Refer to Tables 35-37 and Fig. 47 for unit troubleshooting
information.

II. ECONOMI$ER IV TROUBLESHOOTING

See Table 38 for EconoMi$er IV logic.

A functional view of the EconoMi$er IV is shown in Fig. 48.
Typical settings, sensor ranges, and jumper positions are
also shown. An EconoMi$er IV simulator program is avail-
able from Bryant to help with EconoMi$er IV training and
troubleshooting.

A. EconoMi$er IV Preparation

This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.

NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied
with the EconoMi$er IV.

IMPORTANT: Be sure to record the positions of all potenti-
ometers before starting troubleshooting.

1. Disconnect power at TR and TR1. All LEDs should be

off. Exhaust fan contacts should be open.

2. Disconnect device at P and P1.

Fig. 46 — Spark Adjustment

LOW HEAT

580F036-073 — 74,000 BTUH INPUT

580F036-060 (Low NO

x

) — 60,000 BTUH INPUT

MEDIUM AND HIGH HEAT

580F036-073 — 115,000 BTUH INPUT
580F048-073 — 150,000 BTUH INPUT

580F036-060 (Low NO

x

) — 90,000 BTUH INPUT

580F048-060 (Low NO

x

) — 120,000 BTUH INPUT

Advertising