Table 38 — EconoMi$er IV Input/Output Logic

*For single enthalpy control, the module compares outdoor enthalpy

to the ABCD set point.

†Power at N terminal determines Occupied/Unoccupied setting:

24 vac (Occupied), no power (Unoccupied).

**Modulation is based on the supply air sensor signal.

††Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply air sensor

signals, between minimum position and either maximum position
(DCV) or fully open (supply air signal).

†††Modulation is based on the greater of DCV and supply air sensor

signals, between closed and either maximum position (DCV) or fully
open (supply air signal).

INPUTS

OUTPUTS

Demand Control

Ventilation (DCV)

Enthalpy*

Y1

Y2

Compressor

N Terminal†

Outdoor

Return

Stage

1

Stage

2

Occupied

Unoccupied

Damper

Below set
(DCV LED Off)

High
(Free Cooling LED Off)

Low

On

On

On

On

Minimum position

Closed

On

Off

On

Off

Off

Off

Off

Off

Low
(Free Cooling LED On)

High

On

On

On

Off

Modulating** (between min.
position and full-open)

Modulating** (between
closed and full-open)

On

Off

Off

Off

Off

Off

Off

Off

Minimum position

Closed

Above set
(DCV LED On)

High
(Free Cooling LED Off)

Low

On

On

On

On

Modulating†† (between min.
position and DCV maximum)

Modulating†† (between
closed and DCV
maximum)

On

Off

On

Off

Off

Off

Off

Off

Low
(Free Cooling LED On)

High

On

On

On

Off

Modulating***

Modulating†††

On

Off

Off

Off

Off

Off

Off

Off

Fig. 48 — EconoMi$er IV Functional View