System refrigerant pressure chart – Bard CHDM Dehumidification Module CH3S1 User Manual

Page 7

Advertising
background image

Manual 2100-506D
Page

7 of 14

High Side Pressure:±5°

evacuated, and recharged to serial plate instructions.

Capacitor for Compressor/Blower Motor: Part #8552-085, 15/5 MFD 370V

SYSTEM REFRIGERANT PRESSURE CHART

Low Side pressure: ±2°

Table is based upon rated CFM (airflow) across the Evaporator
Coil. If there is any doubt as to the correct operating charge
being in the system, the charge should be removed, system

7961-679

50% RH

55% RH

60% RH

65% RH

70% RH

75% RH

80% RH

Low Side

96

97

98

100

102

104

106

High Side

248

253

258

261

265

269

273

Low Side

110

112

114

116

117

118

120

High Side

270

276

282

288

294

298

303

Low Side

115

119

123

127

132

136

140

High Side

297

306

315

324

333

342

351

Low Side

120

127

134

141

148

153

158

High Side

342

349

356

363

370

375

380

75° DB

80° DB

85° DB

Relative Humidity %

Return Air

Temperature

Pressure

70° DB

TABLE 2

CHARGING PRESSURE LABEL

Advertising