High voltage wiring connections, Low voltage wiring connections, Wire routing instructions – Bard CHDM Dehumidification Module CH3S1 User Manual

Page 9

Advertising
background image

Manual 2100-506D
Page

9 of 14

Black

Black/White

terminal block

Purple

Red/White

Purple/White

Red

B

lack

Red

Red

High Voltage Wiring Connections

Insert wires

through bushing

and attach to

low voltage

MIS-2454 C

Low Voltage Wiring Connections

Run wires to terminal block

close.

for 460 Volt unit control panel

to ground lug

Control

L3

L2

L2

230 Volt 3 Phase

Connection

L1

L1

Run wires to terminal block

Step Down Transformer

Panel

460 Volt 3 Phase Connection

Wire Routing Instructions

for 230 Volt unit control panel

Dehumidifier

230 Volt Single Phase

Connection

bushing and

(See Wiring Diagram)

Remove
knockout and
insert strain
relief bushing
from opposite
side of panel.
Run wires into

240 Volt

Supply From

Route green ground wire

B

lack

To "L1"

To "Y1"

To "L2"

To "L1"

To "C"

To "DH"

To "R"

To "L3"

To "L1"

To "L2"

Orange

NOT USED (TAPE OFF)

Terminal Block 64

FIGURE 2