Warning, Make electrical connections, Compressor crankcase heater – Bryant 127A User Manual

Page 4: Airflow selections (ecm furnaces)

Advertising
background image

4

Table 2 – Accessory Usage

ACCESSORY

REQUIRED FOR LONG LINE

APPLICATIONS*

REQUIRED FOR

SEA COAST

APPLICATIONS

(Within 2 miles/3.22 km)

Ball Bearing Fan Motor

No

No

Compressor Start Assist Capacitor and Relay

Yes

No

Crankcase Heater

Yes

No

Evaporator Freeze Thermostat

No

No

Hard Shut---Off TXV

Yes

Yes

Liquid Line Solenoid Valve

No

No

Motor Master

®

or Low---ambient Pressure Switch

No

No

Support Feet

No

Recommended

Winter Start Control

No

No

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Split---System Longline

Application Guideline.

{

Additional requirement for Low---Ambient Controller (full modulation feature) MotorMasterr Control.

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit
protection device.
NOTE: Operation of unit on improper line voltage constitutes
abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.
NOTE: Use copper wire only between disconnect switch and unit.
NOTE: Install branch circuit disconnect of adequate size per NEC
to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit

control box.

!

WARNING

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES

CONTACTOR

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

A94025

Fig. 5 -- Line Connections

Connect Control Wiring

Route 24--v control wires through control wiring grommet and
connect leads to control wiring (See Fig. 7). Refer to Installation

Instructions packaged with thermostat.

Use No. 18 AWG color--coded, insulated (35_C minimum) wire. If
thermostat is located more than 100 ft. (30.48 m) from unit, as

measured along the control voltage wires, use No. 16 AWG
color--coded wire to avoid excessive voltage drop.
All wiring must be NEC Class 1 and must be separated from

incoming power leads.
Use furnace transformer, fan coil transformer, or accessory

transformer for control power, 24v/40va minimum.
NOTE:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load with
an accessory transformer as required.

Final Wiring Check

IMPORTANT: Check factory wiring and field wire connections
to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a

minimum of 24 hr before starting unit. To furnish power to heater
only, set thermostat to OFF and close electrical disconnect to

outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than

80 ft. (24.38 m). Refer to the Application Guideline and Service

Manual

Longline

Section--Residential

Split--System

Air

Conditioners and Heat Pumps.

Airflow Selections (ECM Furnaces)

The ECM Furnaces provide blower operation to match the
capacities of the compressor during high and low stage cooling

operation. Tap selections on the furnace control board enable the

installing technician to select the proper airflows for each stage of
cooling. Below is a brief summary of the furnace airflow

configurations

1. The Y2 call for high stage cooling energizes the “Cool” tap

on the control board. The grey wire from cool tap is connec-
ted to tap 5 on the motor. Refer to the furnace Product Data

to find the corresponding airflow. If the airflow setting for
high cooling needs to be switched from tap 5 to a different
tap, jumper a connection from the cool tap to the desired tap

so that the Y2 signal is communicated via the cool tap to the
desired speed tap.

2. The Y1 call for low stage cooling energizes the “Fan” tap

on the control board. The red wire from the fan tap is con-
nected to tap 1 on the motor. Refer to the furnace Product

Data to find the corresponding airflow. If the airflow setting
for low cooling needs to be switched from tap 1 to a differ-

ent tap, jumper a connection from the Fan tap to the desired
tap so that the Y1 signal is communicated via the Fan tap to
the desired speed tap. The Y1 setting will also govern the

continuous fan airflow for the furnace.

Refer to the literature for the furnace for further details.

127A

Advertising