Chapter

6

6-5

Calibration voltage (ADAM-5017/5018)

Module

Input Range Code
(Hex)

Input Range

Span Calibration
Voltage

00h

±15 mV

+15 mV

01h

±50 mV

+50 mV

02h

±100 mV

+100 mV

03h

±500 mV

+500 mV

04h

±1 mV

+1 V

05h

±2.5 V

+2.5 V

06h

±20 mV

+20 mA (1)

0Eh

J thermocouple 0 to
1370°C

+50 mV

0Fh

K thermocouple 0 to
1370°C

+50 mV

10h

T thermocouple -100 to
400°C

+22 mV

11h

E thermocouple 0 to
1000°C

+80 mV

12h

R thermocouple 500 to
1750°C

+22 mV

13h

S thermocouple 500 to
1800°C

+22 mV

5018

14h

B thermocouple 500 to
1800°C

+152 mV

07h

Not used

08h

ºC

±10 V

+10 V

09h

±5 V

+5 V

0Ah

±1 V

+1 V

0Bh

±500 mV

+500 mV

0Ch

±150 mV

+150 mV

5017

0Dh

±20 mA

+20 mV (1)

Table 6-1: Calibration voltage of ADAM-5017/5018