Warning – Bryant 548J*14D User Manual

Page 14

Advertising
background image

14

the transformer; however, the conduit must be routed so

that all wiring is either in the conduit or behind the access

panel.

If the convenience outlet transformer is connected to the

line side of the factory disconnect option, route the wires

through the web bushing located on the bottom of the

disconnect box. For the load side wiring to the factory

option disconnect, route the wires through the hole on the

right side of the disconnect. Be sure to create a drip loop

at least 6” long.

Duty Cycle: the unit--powered convenience outlet has a

duty cycle limitation. The transformer is intended to

provide power on an intermittent basis for service tools,

lamps, etc; it is not intended to provide 15--amps loading

for continuous duty loads (such as electric heaters for

overnight use). Observe a 50% limit on circuit loading

above 8--amps (i.e., limit loads exceeding 8--amps to 30

minutes of operation every hour).

Test the GFCI receptacle by pressing the TEST button on

the face of the receptacle to trip and open the receptacle.

Check for proper grounding wires and power line phasing

if the GFCI receptacle does not trip as required. Press the

RESET button to clear the tripped condition.

C08283

UNIT

VOLTAGE

CONNECT

AS

PRIMARY

CONNECTIONS

TRANSFORMER

TERMINALS

208,

230

240

L1: RED +YEL

L2: BLU + GRA

H1 + H3

H2 + H4

460

480

L1: RED

Splice BLU + YEL

L2: GRA

H1

H2 + H3

H4

575

600

L1: RED

L2: GRA

H1

H2

Fig. 24 -- Unit Powered Convenience Outlet Wiring

Fuse on power type: The factory fuse is a Bussman

“Fusetron” T--15, non--renewable screw--in (Edison base)

type plug fuse.

ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal

injury or death.
Using unit--mounted convenience outlets: Units with

unit--mounded convenience outlet circuits will often

require that two disconnects be opened to de--energize

all power to the unit. Treat all units as electrically

energized until the convenience outlet power is also

checked and de--energization is confirmed. Observe

National Electrical Code Article 210, Branch Circuits,

for use of convenience outlets.

!

WARNING

Installing Weatherproof Cover: A weatherproof

while-in-use cover for the factory-installed convenience

outlets is now required by UL standards. This cover

cannot be factory-mounted due its depth; it must be

installed at unit installation. For shipment, the

convenience outlet is covered with a blank cover plate.

The weatherproof cover kit is shipped in the unit’s control

box. The kit includes the hinged cover, a backing plate

and gasket.

DISCONNECT

ALL

POWER

TO

UNIT

AND

CONVENIENCE OUTLET.

Remove the blank cover plate at the convenience outlet;

discard the blank cover.

Loosen the two screws at the GFCI duplex outlet, until

approximately

1

/

2

-in (13 mm) under screw heads are

exposed. Press the gasket over the screw heads. Slip the

backing plate over the screw heads at the keyhole slots

and align with the gasket; tighten the two screws until

snug (do not over-tighten).

Mount the weatherproof cover to the backing plate as

shown in Fig. 25. Remove two slot fillers in the bottom of

the cover to permit service tool cords to exit the cover.

Check for full closing and latching.

RECEPTACLE
NOT INCLUDED

COVER – WHILE-IN-USE
WEATHERPROOF

BASE PLATE FOR
GFCI RECEPTACLE

C09022

Fig. 25 -- Weatherproof Cover Installation

548J

*14D