To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

sensor. See Fig. 42. Connect the 4--20 mA terminal to

RTU--MP J4--2 and connect the SIG COM terminal to

RTU--MP J4--3. See Fig. 43.

SEN

COM

J4-2

J4-3

IAQ Sensor

24 VAC

C08462

Fig. 43 -- RTU--MP / Indoor CO

2

Sensor

(33ZCSENCO2) Connections

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus

weatherproof enclosure) —

The outdoor air CO

2

sensor is designed to monitor carbon

dioxide (CO

2

) levels in the outside ventilation air and

interface with the ventilation damper in an HVAC system.

The OAQ sensor is packaged with an outdoor cover. See

Fig. 44. The outdoor air CO

2

sensor must be located in the

economizer outside air hood.

COVER REMOVED

SIDE VIEW

C07135

Fig. 44 -- Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO

2

Sensor: A dedicated

power supply is required for this sensor. A two--wire cable

is required to wire the dedicated power supply for the

sensor. The two wires should be connected to the power

supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

OAQ sensor. See Fig. 42. Connect the 4 to 20 mA

terminal to RTU--MP J4--5. Connect the SIG COM

terminal to RTU--MP J4--6. See Fig. 45.

SEN

COM

J4-5

J4-6

OAQ Sensor/RH Sensor

24 VAC

C08463

Fig. 45 -- RTU--MP / Outdoor CO

2

Sensor

(33ZCSENCO2) Connections

On 548J*14D units equipped with factory--installed Smoke

Detector(s), the smoke detector controller implements the

unit shutdown through its NC contact set connected to the

unit’s CTB input. The FSD function is initiated via the

smoke detector’s Alarm NO contact set. The RTU--MP

controller communicates the smoke detector’s tripped status

to the BAS building control. See Fig. 35, RTU--MP System

Control wiring schematic.

The

Fire

Shutdown

Switch

configuration,

MENU

Config

Inputs

input 5, identifies the normally

open status of this input when there is no fire alarm.

Connecting Discrete Inputs —

Filter Status:

The filter status accessory is a

field--installed accessory. This accessory detects plugged

filters. When installing this accessory, the unit must be

configured

for

filter

status

by

setting

MENU

Config

Inputs

input 3, 5, 8, or 9 to Filter

Status and normally open (N/O) or normally closed (N/C).

Input 8 or 9 is recommended for easy of installation. Refer

to Fig. 33 and Fig. 35 for wire terminations at J5.

Fan Status:

The fan status accessory is a field--installed

accessory. This accessory detects when the indoor fan is

blowing air. When installing this accessory, the unit must be

configured

for

fan

status

by

setting

MENU

Config

Inputs

input 3, 5, 8, or 9 to Fan Status

and normally open (N/O) or normally closed (N/C). Input 8

or 9 is recommended for easy of installation. Refer to

Fig. 33 and Fig. 35 for wire terminations at J5.

Remote Occupancy:

The remote occupancy accessory

is a field--installed accessory. This accessory overrides the

unoccupied mode and puts the unit in occupied mode.

When installing this accessory, the unit must be

configured

for

remote

occupancy

by

setting

MENU

Config

Inputs

input 3, 5, 8, or 9 to Remote

Occupancy and normally open (N/O) or normally closed

(N/C).
Also set MENU

Schedules

occupancy source to DI

on/off. Input 8 or 9 is recommended for easy of

installation. Refer to Fig. 33 and Table 2 for wire

terminations at J5.