Installation – Breckwell W3000 User Manual

Page 6

Advertising
background image

Several issues must be addressed when selecting a suitable location for your
W3000 wood stove. Observing required clearances to combustible materials, the
proximity to a safe chimney, and electrical supply (if optional blower in use) must all
be considered. In addition, selecting a location that takes advantage of the building’s
natural air flow is also desirable to maximize the heating effectiveness of the heater.
In many cases, this is a central location within the building.

SPECIFICATIONS


FREESTANDING:
Width: 26”
Height: 29 ½”
Depth: 21 ¾” (total - from face)
Weight: 430 lbs.
Flue size: 6”
EPA status: Non-Catalytic – 2.28 Grams Per Hour
Burn time: 7 – 9 hours
BTU range: 9,500 to 37,000 BTU’s/hr
Approved installations:

FIREPLACE INSERT:
Width: 22 7/8” (at fireplace rear)
26” (at fireplace opening)
Height: 20” (in fireplace)
Depth: 21 ¼” (total – from face)
12 ¾” (in fireplace)
Flashing Size: 40 ½” W x 26 5/8” H (medium)

48 ½” W x 30 5/8” H (large)

Weight: 430 lbs.

Flashing: 13 lbs.

Flue size: 6”
EPA status: Non-Catalytic – 2.28 Grams Per Hour
Burn time: 7 – 9 hours
BTU range: 9,500 to 37,000 BTU’s/hr
Approved installations: zero-clearance, masonry

CLEARANCES

W3000FS


The stove must be placed on a continuous (grouted joints) noncombustible material
such as ceramic tile, cement board, brick, 3/8” millboard or equivalent ½” material
with a k+ .84 insulation factor, or other approved or listed material suited for floor
protection. Check local codes for approved alternatives. Clearances for floor
protection are measured from the sides, back, and face (door opening) as shown in
figure 1.

Minimum clearance to combustibles must be maintained as shown in figure 2 and
the following chart.

A

B*

C

D*

E*

F

G

H

Single Wall

Connector

24”

14”

16”

14”

7”

16”

84”

30”

Double Wall

Connector

22”

12 ½”

12”

10”

7”

16”

84”

30”

Alcove with

Double Wall

22”

12 ½”

12”

10”

7”

16”

84”

30”

Mobile Home

Double Wall

22”

12 ½”

12”

10”

7”

16”

84”

30”

*Given for reference only. Always maintain the clearances listed to the pipe.

W3000I


Minimum clearances to combustibles must be maintained as shown in figure 3 and
the following chart. NOTE: Materials projecting more than ¾” from the wall are
considered mantels.

I

J

K

L

M

N

O

P

W3000I

24”

32”

18”

9”

19 15/16”

4 9/16”

8 ½”

12 5/8”

W3000I

w/Heat Shield*

16”

24”

18”

9”

19 15/16”

4 9/16”

8 ½”

12 5/8”

*Use only the Breckwell Heat Shield – Part Number CW-S-157.

The floor in front of the stove must be protected as
shown in figure 2 and as listed below. The floor
protection must also extend 8” to either side of the
door opening.

When hearth protection is a minimum of 2” high (Q),
The depth (R) must be a minimum of 24”

When hearth protection is a minimum of 4” high (Q),
The depth (R) must be a minimum of 21”

When hearth protection is a minimum of 6” high (Q),
The depth (R) must be a minimum of 18”

When the stove is installed in factory built fireplaces,
2” of clearance must be maintained under the
portion of the insert that extends out over the hearth
extension.

DO NOT USE MAKESHIFT MATERIALS OR
COMPROMISES IN THE INSTALLATION OF THIS
UNIT.

INSTALL VENT WITH CLEARANCES SPECIFIED
BY THE VENT MANUFACTURER.





INSTALLATION

FIGURE 1

FIGURE 2

6

Advertising