Problem

Possible Cause

Solution

Water runs
continuously and
stops when object
present

Connector between
electronics module and
solenoid valve plug is
reversed

Plug connector properly

Water runs
continuously

Interfering object is in
monitoring range

Remove object from monitoring area
Remove and re-install shut-off screw. Do not disturb sensor scanning
procedure (wait until water fl ow stops and LED switches off)

Defective electronics module

Replace electronics module (See “Replacement Parts”)

Improper sensor mode

Change mode or reset sensor (See “Care and Maintenance”)

External water pressure too
high

Check external water pressure
Provide pressure between 20 - 125 psi

Solenoid valve inoperable

Replace solenoid valve (See “Replacement Parts”)

Water fl ows although
shut-off screw is
removed

Electronics module is
inoperable

Replace electronics module (See “Replacement Parts”)

Water drops on infrared
window

Clean window with smooth cloth

Faucet turns on by
itself

Infrared window is dirty or
scratched

Clean window with smooth cloth

Input line pressure fl uctuates

Install appropriate line pressure regulators

Faucet is leaking
water

Connections between
housing and braided hoses
are loose

Check O-rings

Replace O-rings when damaged or missing

Connection between braided
hose and inlet supply are
loose

Check rubber washers

Replace washers when damaged or missing

Connection between valve
body and solenoid valve is
loose

Check O-rings

Replace O-rings when damaged. Carefully reinstall solenoid valve and
do not overtighten.

Faucet drips, solenoid valve
does not close properly

Clean or replace solenoid valve (See “Replacement Parts”)

Temperature cannot
be adjusted properly

No, or too little hot or cold
water. Supply valves are not
fully opened

Fully open supply valves

Inlet water line fi lter is dirty or
blocked

Clean or replace fi lter (See “Care and Maintenance”)

Braided hose is kinked

Eliminate braided hose kink

Backfl ow preventer in faucet
inlet is blocked

Unblock backfl ow preventer

Temperature of hot or cold
water supply is too low

Check inlet water temperature or inspect boiler

Hot water temperature not
suffi cient

Reverse hot water limiter (See “Care and Maintenance”)

Braided hoses are connected
improperly (cold to hot and
hot to cold)

Correct the connections