How to locate chimney exit, and install, Figure 36, Figure 37 – New Buck Corporation 261 User Manual

Page 45: Figure 38

Advertising
background image










Take measurements from bottom of heater, and use them to locate the
opening for the out side air duct, place them onto protective pad.













HOW TO LOCATE CHIMNEY EXIT, AND INSTALL

Ceiling Exit (Using Close Clearance listed chimney)

1. Suspend a plumb bob from the ceiling above the unit so that the weight is hanging in the

center of the flue exit. ( A small weight on a string will serve as a plumb bob.) Mark
the ceiling where the string is suspended to locate the center of the chimney hole.

Optional air inlet plate opening on outer bottom of unit.

24" min.
(610 mm)

OUTSIDE AIR DUCT THROUGH FLOOR WHEN
MOBLE HOME IS NOT UNDERPENNED

RAIN CAP

FLASHING

RADIATION SHIELD

24" min.
(610 mm)

OUTSIDE AIR DUCT THROUGH UNDERPENNED

RAIN CAP

FLASHING

RADIATION SHIELD

36" TYP.

36" TYP.

20 FT. MAX.

OUT SIDE AIR

OUT SIDE AIR DUCT THROUGH FLOOR WHEN

MOBILE HOME IS NOT UNDERPINNED

OUT SIDE AIR DUCT THROUGH FLOOR WHEN

MOBILE HOME IS UNDERPINNED

Figure 36

Pry ,and twist out inner tab till it breaks loose.

Outer Bottom Of Unit

PROTECTIVE PAD

4-1/4” OUT SIDE AIR

DUCT HOLE

MEASUREMENT

Figure 37

RADIATION

SHIELD

RAIN CAP

RAIN CAP

FLASHING

FLASHING

RADIATION

SHIELD

MEASUREMENT

20 ft. MAX

36" TYP.

24" min.(610mm)

24" min.(610mm)

36" TYP.

Figure 38

43

Advertising