FIGURE 7

CALL FOR BLOWER OPERATION

ECONOMIZER SEQUENCE OF
OPERATION

CONDITION A — COOL OUTDOORS

First stage cooling closes and powers the economizer
dampers to economizer mode and the indoor blower
starts. Mixed Air Sensor senses a mixture of return air
and outdoor air and modulates the dampers accordingly.
Compressor operation is inhibited. (See Figure 7.)

If second stage closes on the thermostat, the dampers
return to the closed or minimum position setting and the
compressor starts for mechanical cooling.