3 15 amp fuse, 4 5 amp fuse, 5 set exercise time switch – Bryant Liquid-Cooled User Manual

Page 15: 6 system ready led

Advertising
background image

Bryant

13

3.1.3 15 AMP FUSE

This fuse protects the control console’s DC control
circuit against electrical overload and is located inside
the control panel. If the fuse has melted open because
of an overload, engine cranking and startup cannot
occur. If the fuse needs to be replaced, use only an
identical 15-amp replacement fuse (type ATO).

3.1.4 5 AMP FUSE

This fuse protects the battery charger against electri-
cal overload and is located inside the control panel. If
the fuse needs to be replaced, use only an identical 5-
amp replacement fuse (type ATO).

NOTE:

This fuse will not remove the + battery input
power from the PCB when it opens. This means
the exercise timer will not be reset.

3.1.5 SET EXERCISE TIME SWITCH

This switch allows programming the generator to
start and exercise automatically. “See Weekly
Exercise Cycle.”

3.1.6 SYSTEM READY LED

The System Ready LED (green) has two main pro-
poses. First, the LED will be ON when the
AUTO/OFF/MANUAL switch is in the AUTO position,
utility is present, and there are no system alarms.
This ON state indicates the system is fully ready for
automatic operation.

The system ready LED will be OFF when the switch
is in the manual or OFF positions.

The system ready LED is also used to indicate the
presence of utility sensing at the PCB when the switch
is either in the AUTO or MANUAL modes. The LED
will flash at the rate of 1/2 second on, 1/2 second off
if the utility sensing level is below the transfer back
threshold.

This secondary function is only available with dip
switch two in the OFF position (ATS - automatic
transfer switch application).

‹

‹

‹

‹

Section 3 - Operation

Bryant Liquid-cooled 25 kW Generator

Condition

System

Low

Low

High

Over

Over

Switch Position

Ready (Green)

Bat (Red)

Oil (Red)

Temp (Red)

Speed (Red)

Crank (Red)

Manual

Auto

Off

Generator Switch is

OFF

X

OFF

OFF

OFF

OFF

O

in the OFF Mode.

System Ready for

ON

X

OFF

OFF

OFF

OFF

O

Automatic Start

Generator Switch is

OFF

X

OFF

OFF

OFF

OFF

O

in the MANUAL Mode

Weekly Exerciser

X

Flashing

Flashing

Flashing

Flashing

Flashing

O

O

O

is not set

(-----------------------------------1 sec rate---------------------------------------)

Battery Voltage <12V

X

ON

O

O

O

for >1 minute

(Non-latching)

Battery Voltage <6V

X

ON

O

O

Unit Shutdown due

OFF

X

ON

O

O

to Low Oil Pressure

Unit Shutdown due

OFF

X

ON

O

O

to High Temperature

Unit Shutdown due

OFF

X

ON

O

O

to Engine Overspeed

Unit Failed to Start

OFF

X

ON

O

O

during it’s Crank Cycle

Utility Voltage is

Flashing

X

O

O

<45% of Nominal

1 sec rate

Engine Speed Signal Fault

OFF

X

Flashing

O

O

Control Board Dip Switch

OFF

X

The five RED LED’s will turn on one at a time

O

O

O

is in wrong position.

X = indicates that the LED can be ON or OFF depending on the operating conditions.