GUIDE SPECIFICATIONS

Packaged Heat Pumps
Constant Volume Application

HVAC Guide Specifications
Size Range:1-1/2 to 5 Tons, Nominal Cooling
Bryant Model Number: 601A
Part 1—General

SYSTEM DESCRIPTION

Outdoor packaged air to air heat pump unit utilizing a her-

metic compressor for cooling duty and optional electric
heating. Unit shall discharge supply air vertically or horizon-
tally as shown on contract drawings. Outdoor fan/coil sec-
tion shall have a draw-thru design with vertical discharge for
minimum sound levels.

QUALITY ASSURANCE

A. Unit shall be rated in accordance with ARI Standards 210/

240-94 and 270-95.

B. Unit shall be designed in accordance with UL Standard

1995.

C. Unit shall be manufactured in a facility registered to ISO

9001 manufacturing quality standard.

D. Unit shall be UL listed and c-UL certified as a total package

for safety requirements.

E. Roof curb shall be designed to conform to NRCA Stan-

dards.

F. Insulation and adhesives shall meet NFPA 90A require-

ments for flame spread and smoke generation.

G. Cabinet insulation shall meet ASHRAE Standard 62P.

DELIVERY, STORAGE AND HANDLING

Unit shall be stored and handled per manufacturer’s rec-

ommendations.

Part 2 — Products
EQUIPMENT

A. General:

Factory-assembled, single-piece, heat pump unit. Con-
tained within the enclosure shall be all factory wiring, pip-
ing, controls, refrigerant charge (R-22), and special
features required prior to field start-up.

B. Unit Cabinet:

1. Unit cabinet shall be constructed of phosphated, zinc-

coated, pre-painted steel capable of withstanding 500
hours of salt spray.

2. Normal service shall be through a single removable

cabinet panel.

3. The unit shall be constructed on a rust proof unit base

that has an externally trapped, integrated sloped drain.

4. Indoor fan compartment top surface shall be insulated

with a minimum 1/2-in. thick, flexible fiberglass insula-
tion, coated on the air side and retained by adhesive
and mechanical means. The indoor wall sections will
be insulated with a minimum semi-rigid foil-faced board
capable of being wiped clean. Aluminum foil-faced fi-
berglass insulation shall be used in the entire indoor air
cavity section.

5. Unit shall have a field-supplied condensate trap.
6. Metal Insulated Duct Covers for side discharge will be

standard on all sizes.

7. Unit Insulation conforms to ASHRAE 62P.

C. Fans:

1. The indoor fan shall be 3-speed, direct-drive, as shown

on equipment drawings.

2. Fan wheel shall be made from steel and shall be dou-

ble-inlet type with forward curved blades with corrosion

resistant finish. Fan wheel shall be dynamically bal-
anced.

3. Outdoor fan shall be direct drive propeller type with alu-

minum blades riveted to corrosion resistant steel spi-
ders, be dynamically balanced, and discharge air
vertically.

D. Compressor:

1. Fully hermetic compressors with factory-installed vibra-

tion isolation.

2. Reciprocating or scroll compressors shall be standard

on all units.

3. Compressor Protection:

Defrost control shall protect compressor by preventing
“short cycling.”

E. Coils:

Indoor and outdoor coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all
joints brazed. (Copper/copper and vinyl-coated construc-
tion available as option.) Tube sheet openings shall be
belled to prevent tube wear.

F. Refrigerant Metering Device:

Refrigerant metering device shall be of the fixed orifice
feed type.

G. Filters:

Filter section shall consist of field-installed, throwaway, 1-in.
thick fiberglass filters of commercially available sizes.

H. Controls and Safeties:

1. Unit controls shall be complete with a self-contained

low voltage control circuit.

2. Units shall incorporate an internal compressor protec-

tor that provides reset capability.

I.

Operating Characteristics:
1. Unit shall be capable of starting and running at 125°F

ambient outdoor temperature per maximum load crite-
ria of ARI Standard 240-94.

2. Compressor with standard controls shall be capable

of operation down to 40°F ambient outdoor tempera-
ture in cooling mode.

3. Unit shall be provided with 60-second fan time delay af-

ter the thermostat is satisfied.

J. Electrical Requirements:

All unit power wiring shall enter the unit cabinet at a single

location.

K. Motors:

1. Compressor motors shall be of the refrigerant-cooled type

with line-break thermal and current overload protection.

2. All fan motors shall have permanently lubricated bear-

ings, and inherent, automatic reset, thermal overload
protection.

3. Condenser fan motor shall be totally enclosed.

L. Special Features Available:

1. Grille:

Wire grille shall be standard on all units. Louvered grille

shall be available as a factory-installed option to pro-
vide hail guard and vandalism protection.

2. Coil Options:

Shall include factory-installed optional copper/cop-

per and vinyl-coated refrigerant coils.

3. Economizer:

a. Economizer controls capable of providing free cool-

ing using outside air.

b. Equipped with low leakage dampers not to exceed

3% leakage, at 1.0 in. wg pressure differential.