Warning – Bryant 569J User Manual

Page 17

Advertising
background image

17

Preliminary Charge —

Before starting the unit, charge R-410A liquid refrigerant

into the high side of each 569J circuit through the liquid

service valve(s). The amount of refrigerant added must be

at least 80% of the operating charge listed in Tables 5 or 6

for LINEAR line length LESS the factory charge quantity

(if factory shipping charge has not been removed). See

example below.

Allow high and low side pressures to equalize. If pressures

do not equalize readily, charge R-410A vapor (using spe-

cial service manifold with expansion device) into the suc-

tion line service port for the low side of system to assure

charge in the evaporator. Refer to GTAC II, Module 5,

Charging, Recover, Recycling, and Reclamation for liquid

charging procedures.

Example:
569J*12A/B (Novationt)
60-ft (18.3 m) linear line length
Equivalent line length 90-ft (27.4 m)
Liquid Lift: 20-ft (6.1 m)
Select line sizes from Table 5 (569J***A/B):

Liquid

1

/

2

in

Suction 1

1

/

8

in.

Charge 17.3 lbs (at 75--ft linear length)

80% of Operating Charge:

0.80 x 17.3 = 13.8 lbs

Factory Shipping Charge: 6.3 lbs
Field-Charge quantity: 13.8 -- 6.3 = 7.5 lbs
For linear line lengths longer than 125 ft (38 m), contact

your local Bryant representative for system charge value.

Step 6 — Install Accessories

Accessories requiring modifications to unit wiring should

be completed now. These accessories may include Winter

Start controls and Low Ambient controls. Refer to the

instructions shipped with the accessory.

Step 7 — Complete Electrical Connections

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Do not use gas piping as an electrical ground. Unit

cabinet must have an uninterrupted, unbroken electrical

ground to minimize the possibility of personal injury if

an electrical fault should occur. This ground may consist

of electrical wire connected to unit ground lug in control

compartment, or conduit approved for electrical ground

when installed in accordance with NEC (National

Electrical Code); ANSI/NFPA 70, latest edition (in

Canada, Canadian Electrical Code CSA [Canadian

Standards Association] C22.1), and local electrical

codes.

!

WARNING

NOTE: Check all factory and field electrical connections

for tightness. Field-supplied wiring shall conform with the
limitations of 63°F (33°C) rise.
Field Power Supply —

If equipped with optional Powered Convenience Outlet:

The power source leads to the convenience outlet’s

transformer primary are not factory connected. Installer

must connect these leads according to required operation

of the convenience outlet. If an always-energized

convenience outlet operation is desired, connect the

source leads to the line side of the unit-mounted

disconnect. (Check with local codes to ensure this method

is acceptable in your area.) If a de-energize via unit

disconnect switch operation of the convenience outlet is

desired, connect the source leads to the load side of the

unit disconnect. On a unit without a unit-mounted

disconnect, connect the source leads to compressor

contactor C and indoor fan contactor IFC pressure lugs

with unit field power leads..

Field power wires are connected to the unit at line-side

pressure lugs on compressor contactor C and TB1 (see

wiring diagram label for control box component

arrangement) or at factory-installed option non-fused

disconnect switch. Max wire size is #4 AWG (copper

only).
NOTE: TEST LEADS - Unit may be equipped with short
leads (pigtails) on the field line connection points on

contactor C or optional disconnect switch. These leads are
for factory run-test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.

FIRE HAZARD
Failure to follow this warning could cause in personal

injury, death and/or equipment damage.
Do not connect aluminum wire between disconnect

switch and condensing unit. Use only copper wire.

(See Fig. 10.)

!

WARNING

COPPER

WIRE ONLY

ELECTRIC

DISCONNECT

SWITCH

ALUMINUM

WIRE

A93033

Fig. 10 -- Disconnect Switch and Unit

Units Without Factory-Installed Disconnect —

When installing units, provide a disconnect switch per

NEC (National Electrical Code) of adequate size.

569J

Advertising