Caution – Bryant 569J User Manual

Page 3

Advertising
background image

3

Same tube sizes are capable of handling higher flowrates

(expressed as tons of cooling capacity) with Puron

refrigerant compared to R--22 at constant pressure drops.

For example, a

1

/

2

--inch OD liquid line is rated at 33%

higher tons with Puron

R

than with R--22 (at 5_F pressure

drop). A 1

1

/

8

--inch OD suction line is rated at 53% higher

tons with Puron than with R--22 (at 2_F pressure drop).

Refrigeration lines selected for R--22 use are typically

oversized for Puron applications. Carefully check the

existing suction line size against the table for maximum size

(see Table 7); replace vertical riser segments if necessary.

Check existing liquid line size against sizing data in Table 5

or 6; replace with smaller lines when feasible.

Installation –

1. Remove the existing evaporator coil or fan coil and

install the replacement coil when appropriate.

2. Drain oil from low points and traps in suction line

tubing (and hot gas bypass tubing if appropriate) and

evaporator if they were not replaced. Removing oil

from evaporator coil may require purging of the

tubing with dry nitrogen.

3. Unless indoor unit is equipped with a Puron® ap-

proved metering device, change the metering device

to a thermal expansion valve (TXV) designed for

Puron

R

(R-410A).

4. Remove the existing outdoor unit. Install the new out-

door unit according to these installation instructions.

5. Install a new field-supplied liquid-line filter drier at

the indoor coil just upstream of the TXV or fix orifice

metering device.

6. If a suction line filter drier is also to be installed, in-

stall suction line drier downstream of suction line ser-

vice valve at condensing unit.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment

damage or improper operation.
Never install suction--line filter drier in the liquid--line

of a Puron

R

system.

CAUTION

!

7. If required, install a 100% activated alumina suction

line filter drier at the outdoor unit.

8. Evacuate and charge the system according to the in-

structions in this installation manual.

9. Operate the system for 10 hr. Monitor the pressure

drop across the suction line filter drier. If pressure

drop exceeds 3 psig (21kPa), replace suction-line and

liquid-line filter driers. Be sure to purge system with

dry nitrogen and evacuate when replacing filter

driers. Continue to monitor the pressure drop across

suction-line filter drier. Repeat filter changes is neces-

sary. Never leave suction-line filter drier in system

longer than 72 hr (actual time).

569J

Advertising