Warning, Installation, Not good good – Advanced Protection SPDee User Manual

Page 2: Figure 3, Figure 2

Advertising
background image

2

LEADS SHOrT & STrAIGHT

X

NOT

GOOD

GOOD

Cut off

Excess Length
Do Not Loop

or Coil

Short

& Straight

Figure 2

A

B

C

G

N

BREAKER

(Type 1 or individual equipment installations may vary)

Use closest

breaker to SPD

Locate SPD close

to intended breaker

Keep Leads Short

as Possible

Avoid Sharp Bends

Rotate SPD

ee

such

that LED indicator

is most visible

Outdoor installation requires appropriate weather

sealing at nipple (gasket, sealing conduit, etc.)

To Protected Loads

Figure 1

Sealing gasket:

two choices

1.) At 3/4" nom.

thread: ID is 1.05"

2.) At 0.14" high 'base

step': ID is 1.25"

Figure 3

INSTALLATION

Pre-Plan your installation. You need to accomplish the following:

Meet all National and Local codes (NEC

®

Article 285 and UL 1449 address SPDs).

Confirm System voltage to SPD voltage (120V SPD will fail instantly on 240V, 277V, etc.).

Mount SPD as close to panel or equipment as possible to keep leads short.

(long leads hurt performance substantially).

Ensure leads are as short and straight as possible, including neutral and ground. If using a

breaker, use a breaker position that is close to the SPD and the panel’s neutral & ground.

If using a breaker, recommended breaker size is 30A due to 10 AWG conductor.

Make sure system is grounded per NEC

®

and clear of faults before energizing SPD.

(inadvertent system problem may fail SPD).

Never Hi-Pot test Any SPD. (will prematurely fail SPD).

1. Use voltmeter to check voltages and ensure correct SPD. See Data Sheet for specs and wire-outs.

2. Determine Mounting method (See Figure 5) – weather resistant equipment may be required.

3. If SPD has optional Dry Contact, pre-plan its installation.

4. Remove power from panel/source. Confirm panel/source is deenergized.

5. Identify breaker location and SPD location. Position SPD such that LED is best visible.

6. Mount SPD – weather resistant applications require additional sealing, o-rings, etc. (not included)

- Remove an appropriately sized knockout from panel.

- Connect conductors as appropriate – short and straight as possible (Hi-Legs are Phase B).

7. Label or mark conductors as appropriate (neutral: white, ground: green, energized: black, hi-leg: orange).

8. Make sure system is bonded per NEC

®

and is clear of hazards or faults before energizing.

(N-G bonding not per NEC

®

will fail SPDs: #1 cause of SPD failures)

9. Energize and confirm proper operation of green LED indicator and/or options.

(Affix supplemental label accessory if appropriate. See Figure 5.)

V

WARNING

Confirm XO N-G Bonding at Upstream Transformer

Do Not Hi-Pot Test

Resulting Damage is not Covered Under Warranty

VERIFY THAT ALL POWER CIRCUITS ARE

DEENERGIZED BEFORE MAKING CONNECTIONS

All electrical connections should be performed by a qualified

(licensed) electrician or technician. All wiring must comply with

the National Electrical Code (NEC

®

) and applicable local codes.

TYPICAL PANEL

INSTALLATION

V

WARNING

Advertising