ee

is a Type 1 SPD. SPD

ee

is suitable for

use almost anywhere (not as a plug-in SPD).

Type 1 SPDs are evaluated more rigorously by

UL 1449 for NEC

®

Article 285 compliance. Type

1 SPDs and their connecting leads have been

evaluated for line side applications without need

for supplemental overcurrent protection. Type 1

SPDs include internal overcurrent protection. As

a generalization, there are practical maintenance

reasons for installing on the load side of the main

overcurrent device (i.e. Type 2 installation). When

connected on load side of main disconnect, we

recommend connecting via a 30A circuit breaker

due to 10 AWG conductors. The circuit breaker

serves as a disconnect switch and provides NEC

®

imposed short circuit protection to the conductors

in Type 2 or 4 applications. (cUL units are Type 2

due to different cUL criteria.)

Simplified Explanation of Operation: SPDs sense

overvoltage and create a momentary short circuit

to redirect harmful surge energy to earth ground.

They reset automatically and wait for the next surge.

This is similar to the pressure relief valve on a water

heater: pressure goes up, valve opens to relieve

pressure and then resets. In an electrical system, an

SPD senses overvoltage, shorts temporarily sending

energy to ground and then resets. SPDs are capable

of repeating this function thousands of times.

Parts List

1 - SPD

ee

suppressor including 3’ (~1m) conductors

1 - 3/4” conduit nut

1 - L bracket mounting kit; includes two panhead

screws

1 - Data Sheet

1 - Installation Sheet (this document)

Most SPD

ees

have demonstrated 200kA &

100kA Short Circuit Current Ratings (SCCR)

including leads. See UL Label markings on SPD

or see Data Sheet for specs.) Supplemental

overcurrent protection is not required to protect

this SPD. However, NEC

®

convention requires

that connecting conductors have overcurrent

protection in Type 2 or 4 applications. Follow

applicable codes.

This device features internal overcurrent and

overtemperature protection that will disconnect

effected surge suppression components at the end

of their useful life, but will maintain power to the load

– now unprotected. If this situation is undesirable

for the application, follow these instructions for

replacing the device. SPD

ee

is ultrasonically welded

closed and contains no user serviceable parts.

Specifications

Temperature Operating

-40

o

C (-40

o

F) to 60

o

C (+140

o

F)

Temperature Storage

-55

o

C (-67

o

F) to 65

o

C (+149

o

F)

Wire Size & Installation Torque 10 AWG; 18 inch-pounds
Appropriate Circuit Breaker

based on conductor size

30A (SPD includes internal OCP)

NEMA 250 Enclosure Rating

Type 4X with appropriate

sealing & sealing condulets

Voltage rating & Application

Before installing SPD, verify by nameplate voltage

or model number that it has the same voltage rating

as the power distribution system. See attached Data

Sheet or call APT Tech Support at (800) 237-4567 as

appropriate. The SPD’s specifier or user should be

familiar with the configuration and arrangement of

the power distribution system. The system is defined

by how the secondary windings of the transformer

supplying the service entrance main or load are

configured. This includes whether or not the transformer

windings are referenced to earth via a grounding

conductor. The system configuration is not based on

how any specific load or equipment is connected to a

particular power distribution system. SPDs should be

installed per the distribution system, not per a load or

motor’s wiring connection.

Bracket Mount

for flat surfaces

Std. 3/4”-14 Nipple

DIN-Rail Mount

(rail not incl.)

Supplemental Product Label may be affixed if standard

top label is not viewable

• 3/4” pipe nipple (conduit nut included)

• With L-bracket mounting kit accessory

- Standard 35mm DIN-Rail (not included)

L-bracket tightens onto DIN-Rail

- Standard flat mounting surface

Attach L-bracket to surface via mounting holes

Figure 5

SPD

ee

MOUNTING OPTIONS

3.26”

3.26”

1.15”

4.13”

3/4”-14

Sized for std 35mm DIN-Rail

3.31” 3.57”

Weight: 1.60 lbs

(0.73 kg)

Figure 4

DIMENSIONS & WEIGHT

3

Advertising