Figure 1 – typical nameplate, Oil supply pressure control required, Correct nozzle and flow rate required – Beckett CF1400 User Manual

Page 5: Nozzle pressure, Electrical supply, Fuel supply

Advertising
background image

5

Form 6104 BCF23-R05

Nozzle pressure

The fuel unit nozzle port pressure is factory set at 300
psig. Some original equipment manufacturer burner
applications may call for a lower pressure to obtain a
required fi ring rate. Do not change this pressure un-
less directed to do so by the appliance manufacturer.

Electrical supply

Verify that the power connections available are correct
for the burner. Refer to Figure 1. All power must be
supplied through fused disconnect switches.

‰

y

‰

Fuel supply

The fuel supply piping and tank must provide #1 or #2
fuel oil at pressure or vacuum conditions suitable for
the fuel unit (oil pump) on the burner. Refer to fuel unit
literature in the literature envelope in the burner carton to
verify allowable suction pressure.
When fuel supply is level with or higher than burner
fuel unit
—When the fuel unit is not required to lift the
oil, the installation is usually suitable for either a one-
pipe or two-pipe oil system. The oil pressure at the inlet
of the fuel unit must not exceed 3 psig.
The fuel unit is shipped with the by-pass plug installed.
Leave the by-pass plug installed for all low/high fi ring
burners, regardless whether one-pipe (with by-pass
loop) or two-pipe
. See Figure 9 for installation of the by-
pass loop
required for one-pipe fuel supply installations.
See Figure 10 for connections to the fuel unit for two-
pipe fuel supply installations.
When fuel supply is below the burner fuel unit —Use
a two-pipe oil system when the fuel unit must lift the oil
more than 8 feet. The return line provided by the two-pipe
system is needed to minimize the effects of air-related
problems during operation.

‰

LISTED

(FUEL) BURNER

SERIAL NUMBER

050214-00000

Control Circ: 120V/60Hz 4.5A

Motor Circ: 120V/60Hz 4.0A

Model “XX”

Series (Fuel) Burner

R.W. Beckett Corp.

Elyria, Ohio

Made in the U.S.A.

For use with Group 8 . . .

MP 1192 XX000 R00

X
X
X
X
X
X

XX000 R00

050214-00000

MFR’S SETTINGS

R.W. Beckett Construction & Setting Data

R.W. Beckett Specifi cation
Number and Revision

Boiler Manufacturer and
Model, When Applicable

Additional Codes

General Model Information

Serial Number,Including Date Code

Rating Information

Approval Agency Symbols

Primary Group and Fuel

L0002

Figure 1 – Typical Nameplate

The oil supply inlet pressure to the burner cannot
exceed 3 psig
.

Insure that a pressure limiting device is installed in
accordance with the latest edition of NFPA 31.

Gravity Feed Systems: Always install an anit-siphon
valve in the oil supply line or a solenoid valve (RWB
Part # 21789) in the pump/nozzle discharge tubing to
provide backup oil fl ow cut-off protection.

y

y

y

Damage to the fi lter or pump seals could cause

oil leakage and a fi re hazard.

Oil Supply Pressure
Control Required

Use only nozzles having the brand, fl ow rate (gph), spray angle

and pattern specifi ed by the appliance manufacturer.

Follow the appliance manufacturer’s specifi cations for the

required pump outlet pressure for the nozzle, since this affects
the fl ow rate.

Nozzle manufacturers calibrate nozzle fl ow rates at
100 psig.
This burner utilizes pressures higher than 100 psig,
so the actual nozzle fl ow rate will be greater than the
gph stamped on the nozzle body. (Example: A 8.00
gph nozzle at 150 psig = 9.80 gph and at 300 psig
= 13.86 gph)

For typical nozzle fl

ow rates at various pressures see

accompanying chart.

y

y

Incorrect nozzles and fl ow rates

could result in impaired combustion,
under-fi ring, over-fi ring, sooting,
puff-back of hot gases, smoke
and potential fi re or asphyxiation
hazards.

Correct Nozzle and Flow

Rate Required