G - Concrete and Backfill Guidelines.

To ensure that no immediate or future damage is done to your Bravo Tank Sump Reducer
components, make sure that your manhole skirt DOES NOT TOUCH OR REST ON THE TANK
SUMP SHOULDER.
The Manhole Skirt should be kept at minimum of 4” away from the tank sump
shoulder. Follow the manhole manufacturers instructions for installing the manhole. Also follow other
details provided by tank and/or engineering firm for tank driveway pad installation.

Backfill your peagravel around the sump maintaining a minimum of 1’ foot all the way around (if your
site backfill is not entirely peagravel) and 4” minimum distance from the top edge of sump reducer.

When peagravel is in place, use a 3mil or thicker plastic sheet to cover the surface of the peagravel
no less than 2 feet away from the sump reducer wall.

Secure this plastic barrier to the

EXTERIOR OF THE MANHOLE SKIRT

using duct tape.

This prevents concrete from seeping too far down
into the peagravel.

Manhole Cover

CONCRETE

SLAB

Manhole skirt

Sump Cover

Min 1’ foot
peagravel all
around sump

1” to 1-1/2”

Distance

3mil+ Plastic Barrier
taped to manhole skirt

SAND

OR SOIL

Minimum

4 inches

between top

of sump

reducer and

peagravel

Manhole

skirt min.

4” away

from Tank

sump

shoulder