13. When the calibrated measuring

container is filled to the required level,

press the red ON/OFF button ( )to

STOP foam flow. (See Figure 5.)

14. Use the INCREASE or DECREASE

buttons ( or ) and set the value to

the known amount of foam collected in

the calibrated measuring container.

15. If the foam is dispensed into a

clean

container, return the concentrate to the

foam tank and place the bypass hose

back into the container.

IMPORTANT !

If the container is NOT clean, the foam becomes
contaminated and must be discarded.

16. Repeat preceding Steps 12 through 14.

17. Press the DISPLAY button (

i

) to view

the foam flow calibration factor. Write

this number down for future reference.

(See Figure 6).

Verify that the foam calibration factor is

between 270 and 310.


Contact customer service at 1-800-533-3569
if the calibration factor does not fall within the
required calibration range.

18. Press and hold the DISPLAY button (

i

)

until PASS is displayed. (See Figure 1

on the preceding page.)

19. With the DISPLAY button (

i

) pressed,

press the INCREASE button ( ) 4 times.

A u is shown with each INCREASE

button press. (See Figure 2 on the

preceding page.)

20. Release the DISPLAY button (

i

). The

display shows ScAL for about 5 seconds.

The unit re-initializes and the calibration

factor is saved. (See Figure 7.)

21. Foam flow calibration is now complete.