OUTLET END

INSERT STRIP ASSEMBLY

INTO LAST 10 FT OF TUBE

INSERT STRIP

ASSEMBLY INTO LAST

10 FT. OF TUBE

OUTLET END

Assemble the strips and insert into last tube. Edge of strip
is flush with end of tube. See Fig. 9. Refer to Fig.10 for
installation of vent hood.

FIG. 9

FIG. 10

MANUAL SHUT-OFF VALVE, HOSE

& REGULATOR ASSEMBLY

REGULATOR

NIPPLE

VALVE, MANUAL
SHUT-OFF

GAS HOSE

ADAPTER

SEDIMENT TRAP

TO CONTROL

VALVE INLET

REGULATOR VENT

GAS FLO

W

1.

Assemble the components together. See Fig. 12.
T h i s v i ew s h ow s g e n e r a l a s s e m b l y o f t h e
components. The regulator must always be mounted
so its vent, regardless of location on the regulator, is
always pointed downward. Ensure hose is positioned
away from the heater.

2.

Tighten all connections securely and check for gas
leaks.

FIG. 12

SECOND STAGE

REGULATOR

13

Assemble the tee, nipple, and cap to the nipple at the gas
inlet of heater. See Fig. 11. Tighten securely. The sediment
trap assembly must always be mounted in a ver tical
position. Check all connections for gas leaks using
approved gas leak detectors.

FIG. 11

TUBE

VENT HOOD

PUSH FIRMLY ONTO END TUBE

AIR TURBULATION STRIPS & VENT HOOD

SEDIMENT TRAP ASSEMBLY

PUSH VENT HOOD FIRMLY ONTO END OF
LAST TUBE, OUTLET DOWN. FLAPPER OF
VENT HOOD MUST CLOSE COMPLETELY.

PLE

HOSE ADAPTER

TEE

NIPPLE

CAP

NIPPLE

FROM HEATER