Installing dust filter, Zone control panel function and installation, Fig. 6 – L.B. White I-34 Infraconic Spark Ignition User Manual

Page 11: Optional), Important

Advertising
background image

INJECTOR BODY TABS

FILTER ADAPTER

PART #23931

BEADED CABLE TIE

DUST FILTER

PART #23953

1100

INSTALLING DUST FILTER

FIG. 6

With proper (5 PSIG) gas pressure supplied, spark ignition

heaters will operate in the standard ON/OFF mode when

electrically connected to a building environment controller or

thermostat

If you require two stages of heat for greater temperature

control, a two stage solenoid operated zone panel must be

installed. This panel incorporates solenoids to control the

first and second stage heating levels as well as a pressure

regulator to set the firing rate of the first stage. Use of this

panel requires a two stage thermostat or a building

controller capable of controlling the heat in two stages.

When energized by a building controller or thermostat, the

zone panel’s first stage solenoid opens providing 2 PSIG,

controlled by the regulator on the zone control panel, to the

heater. This represents approximately half the heater’s full

output. If this level of heating does not satisfy the demand,

the building controller or thermostat will call for the second

stage of heating, full output, by energizing the second stage

solenoid. This provides 5 PSIG to the heater.

As the heat demand is satisfied, the building controller or

thermostat will reduce the firing rate by closing the second

stage solenoid and lastly the first stage solenoid if heat is no

longer needed.

Two stage zone panels are available in high or medium

capacity configurations and will control the following quantity

of heaters depending on fuel type.

All zone control panels must have an adjustable high

pressure regulator installed upstream of the inlet of the

panel. This regulator may be purchased from PSI as an

optional accessory. The regulator must be capable of

handling a maximum inlet pressure of 10 psi, while

supplying an outlet pressure of 5 psi nominal.

Separate installation instructions accompany each zone

panel.

ZONE CONTROL PANEL

FUNCTION AND INSTALLATION

(Optional)

Solenoid Zone Control System

Medium

High

Model and

Capacity

Capacity

Heat Output

Fuel

Panel

Panel

Quantity

Quantity

I34

L. P. Gas

7

20

(34,200 BTUH)

Natural Gas

4

20

INJECTOR

BODY

TABS

FILTER SLEEVE

PART #20421

BEADED

CABLE TIE

DUST FILTER

PART #81649

FILTER SLEEVE

IMPORTANT

This filter kit is designed to provide additional dust filtration

capability and capacity for Infraconic heaters when installed

in severely dusty environments.

1. Attach filter sleeve to injector body. The injector body

tabs fit into the slots on the sleeve. Rotate the sleeve

to lock it onto the injector body.

2. Position the filter onto the sleeve. Ensure all sleeve

holes are covered by the filter.

3. Securely attach the filter to the sleeve using the

beaded cable tie.

4. Ensure filter does not sag or touch heater’s canopy.

FILTER