Trouble-shooting, Clear blockage in pipes, Power unit will not start power unit will not stop – Beam Electrolux Mundo User Manual

Page 7: Power unit shuts off by itself

Advertising
background image

7

TROUBLE-SHOOTING

If you experience trouble with your central
vacuum system, follow the suggestions below
before calling for service.

Partial/total loss of suction power
t Be sure lid is on properly.
t Empty dirt receptacle.
t Clean cartridge lter.
t Be sure each inlet valve is properly closed.
t Check for hose obstruction.

Plug hose into any inlet valve. Then, as you check
each of the other inlet valves, raise the inlet cover

and hold your hand over the opening to check for

suction. If there is normal suction at each inlet,
then insert the hose into one of the other inlets. If

there is no suction through the hose at the second

inlet, the blockage is in the hose. To clear the
hose obstruction, insert a blunt instrument into the

hose (garden hose, wood dowel). If there is one
inlet valve without normal suction and you have
checked for hose blockage, then the blockage is
in the pipe system between the blocked inlet valve

and the power unit (see instructions below).

Clear blockage in pipes

Insert the hose into the inlet valve where there is no

quickly. Repeat several times. If blackage does not clear,

contact your nearest dealer/distributor.

Power unit will not start

Power unit will not stop

t Check inside each inlet valve for obstruction of low-

voltage contacts. If no visual obstruction can be detected,
disconnect the cleaner from the power receptacle and

t Check for blown fuse in main house electric supply box.

t If the green light is flashing, or does not light up, and the

motor does not start, the power unit could have

experienced a fault due to excessively high or low

Power Unit Shuts Off by Itself

Remove and then re-insert the hose into inlet or toggle switch
off/on. See “Motor Protection Shutoff” portion of the user
manual.

DO NOT OIL THE MOTOR AT ANY TIME. IT IS

PERMANENTLY LUBRICATED AND SEALED.

BM 165

BM 185

BM 262

BM 265

BM 285

t If your power unit has a control light, the solid green light

will indicate when when the unit has proper voltage and

the low-voltage circuit is supplying power to the inlets.

standard operating voltage, high current draw, or a
locked rotor. It is also possible that the unit was powered

on with a low-volt connection (ie. handle, vac pan, etc.)

in the ON position. To resolve this issue:

contact your nearest service station/dealer.

a. Ensure all handles and vac pans are in the OFF

position

b. Unplug the power unit cord from the wall outlet,

and then plug in again.

c. Press the on/off button on the power unit.

Should the light be on, but the motor starts only with the

t

on/off button and not at the inlets, the problem is

suction; hold your hand over the hos end. Release hand

broken low-voltage wiring to the wall inlets. Call your

authorized BEAM dealer/distributor.

Advertising