II.

WIRING INSTRUCTIONS

WARNING!

Read Safety Warning, on page 1, before using this control.

Disconnect the AC line before wiring.

Note:

To avoid erratic operation, do not bundle AC line and motor wires with wires from sig-

nal following, Start/Stop Switch or any other signal wires. Use shielded cables on all signal
wiring over 12” (30cm). Shield should be Earth grounded on the control side only. Wire the
control in accordance with the National Electrical Code requirements and other codes that
may apply to your area. See Table 3 and Figure 4, on page 6.

Be sure to properly fuse each AC line conductor that is not at ground potential.

Do not fuse neu-

tral or grounded conductors.

See Section VII, on page 10. A separate AC line switch or con-

tactor must be wired as a disconnect so that each ungrounded conductor is opened. A Power
On/Off Switch may be used in lieu of, or in addition to, the Start/Stop Switch. The switch can be
wired for single pole or double pole operation, as required.

To maintain the watertight integrity of the control, be sure to use suitable watertight connec-
tors and wiring which are appropriate for the application. Two 7/8” (22.2mm) knockout holes
are provided for standard 1/2” knockout connectors (not supplied) for wiring. A watertight
plug is provided if only one knockout is required.

The enclosure is designed with a hinged case so that when the front cover is open, all wiring
stays intact. To open the cover, the four screws must be loosened so they are no longer
engaged in the case bottom. After mounting and wiring, close the cover making sure that the
wires do not get caught or crimped as the cover is closed. Tighten all four cover screws so
that the gasket is slightly compressed.

Do not over tighten.

!

1.5

Parameter

Specification

Output Frequency (Hz)

Minimum Operating Frequency at Motor (Hz)

Factory Setting

AC Line Input Voltage (Volts AC, ±10%, 50/60 Hz)

115 or 208/230

208/230

Maximum Load Capacity (% for 2 Minutes)

150

Switching Frequency (kHz)

8—

Signal Following (Non-Isolated Input

1

) Input Voltage (Volts DC)

0 – 5

Signal Following Input Resolution (Bits)

8—

Maximum Speed Trimpot (MAX) Range (% of Frequency Setting)

70 – 110

100

Minimum Speed Trimpot (MIN) Range (% of Frequency Setting)

0 – 40

0

Acceleration Trimpot (ACCEL) Range (Seconds)

0.3 – 20

1.5

Deceleration Trimpot (DECEL) Range (Seconds)

0.3 – 20

1.5

Slip Compensation Trimpot (COMP) Range (Volts/Hz/Amp)

0 – 3

Current Limit Trimpot (CL) Range (% Range Setting)

0 – 200

160

Boost Trimpot (BOOST) Range for 50 Hz Output Frequency (Volts AC)

0 – 70

Boost Trimpot (BOOST) Range for 60 Hz Output Frequency (Volts AC)

0 – 35

5

Motor Horsepower Selection (HP)

1/4, 1/2, 3/4, 1

1

0 – 50, 0 – 60

0 – 60

1

Speed Regulation (30:1 Speed Range) (% Base Speed)

2

2.5

Speed Range (Ratio)

60:1

Operating Temperature Range (°C)

0 – 45

TABLE 2 – GENERAL PERFORMANCE SPECIFICATIONS

Frequency Multiplier (1X, 2X)

1, 2

1

Notes:

1. Requires an isolated signal. If a non-isolated signal voltage is used, install the ID5SI-2 Signal Isolator.
2. Dependent on motor performance.

TABLE 1 – ELECTRICAL RATINGS

1, (0.75)

Maximum

Horsepower Rating

HP, (kW)

AC Line Input Voltage

±10%, 50/60 Hz

(Single Phase Volts AC)

Maximum Continuous

Output Load Current

(RMS Amps/Phase)

115

Maximum

AC Line Input Current

(Amps AC)

16

Nominal

Output Voltage

(Volts AC)

0 – 230

3.6

208/230

10

0 – 230

3.6

1, (0.75)