Ventless Hood System

Installation

10

Fire Extinguishing System

In the event of an appliance fire, serious injury, property damage or death could
occur if any part of the appliance obstructs the spray nozzles. Ensure that lids
and/or other parts of the appliance do not obstruct the spray pattern of either
nozzle.

The fire extinguishing system components used in this hood have been evaluated
by U.L. in the course of their classification for use on this hood.

An authorized Range Guard

 distributor must install and activate the filter hood

fire extinguishing system. To locate an authorized Range Guard

 Distributor use

the following contact information:

Ronald Woodward
Technical Service Specialist
Badger Fire Protection
4251 Seminole Trail
Charlottesville Va. 22911
Office: 800-446-3857 ext. 111
Fax: 434-974-4113
Mobile: 434-981-0505

1. After the hood has been properly secured to prevent movement, locate the end-of-line remote pull

station (at a point of egress or exit) in a manner approved by the local authority and in
accordance with applicable codes. To install the end-of-line remote, use ½” EMT and Range
Guard

 corner pulleys #97915.

2. Install two UL Listed; type “A”, 165

 F. fusible links (load rating 3-45 lbs.) in the two appliance

detector positions (one in front of the grease baffle, one behind the grease baffle).

3. If required, connect the provided fire extinguishing system contacts for remote signaling (refer to

the electrical diagram in this manual).

4. Adjust the position of the two ADP appliance nozzles as depicted below.

FUSIBLE

LINKS