Blue Sea Systems 7620 ML-ACR Automatic Charging Relay - 12V DC 500A User Manual

Overview of application, Ml– acr, Automatic charging relays

Advertising
background image

ML– ACR

Automatic Charging Relays

PN 7620 / PN 7621

(without manual control)

PN 7622 / PN 7623

(with manual control)

990180180 Rev.004

Blue Sea Systems Inc.

Phone (360) 738-8230

425 Sequoia Drive

Fax (360) 734-4195

Bellingham, WA 98226 USA

[email protected]

www.bluesea.com

• Magnetic Latch (ML)—draws very low current in the ON or OFF states, and draws moderate current for very

short time when changing state

• Start Isolation (SI)—can be configured for temporary isolation of House loads from Engine circuit during engine

cranking to protect sensitive electronics

• Engine Isolation (EI)—can be configured for isolation of two engines while both are running to protect engine

electronics and maximize alternator output

• Senses charging on two battery banks

• LED output to remotely indicate when batteries are combined or isolated

• Tin-plated copper studs for maximum conductivity and corrosion resistance

• Label recesses for circuit identification

• Silver alloy contacts provide high reliability for switching live loads

Specifications

12V DC

24V DC

Cranking Rating

See table below

See table below

Intermittent Rating

See table below

See table below

Continuous Rating

See table below

See table below

ML-Coil Function

Bi-stable

Bi-stable

Amperage Operating Current

<40 mA continuous (control circuit) <40 mA continuous (control circuit)

<7A when changing state (20 ms)

<4A when changing state (20 ms)

Contact Circuit Voltage

16V DC Max.

32V DC Max.

Relay Contact Position:

-Combine (30 sec.)

13.5V

27.0V

-Combine (90 sec.)

13.0V

26.0V

-Open Low (10 sec.)

12.35V

24.7V

-Open Low (30 sec.)

12.75V

25.5V

-Open High

16.2V

32.4V

Live Current Switching

300A@ 12V DC—10,000 Cycles

-

Terminal Stud Size

3/8"-16

3/8"-16

Maximum Terminal Stud Torque

140 in-lb (15.8 N•m)

140 in-lb (15.8 N•m)

Ring Terminal Size

3/8" (M10)

3/8" (M10)

Terminal Ring Diameter Clearance

1.18" (30 mm)

1.18" (30 mm)

Control Circuit Current Draw

<40 mA

<40 mA

PN 2146 Switch

Action

Sustained SPDT ON-OFF-ON

Seals

Internal & External Gasket Panel Seal

Mounting Hole

0.83"x 1.45" (21.08 mm x 36.83 mm)

LED Rating

100,000 hours half-life

Regulatory Meets ISO 8846 and SAE J1171 external ignition protection requirements, CE marked, Rated IP66

Guarantee

Blue Sea Systems stands behind its products for as long as you own them.

Find detailed information at www.bluesea.com/about. For customer service, call 800.222.7617.

Marine Electrical Products

Overview of Application

The ML-Series ACR automatically combines batteries during charging, and isolates batteries when there is no

charging sensed on either battery bank.

ML-Series ACR Function

12 Volt DC Operation

24 Volt DC Operation

Automatically combines battery

banks when sensed voltage

levels are:

Above 13.5V for 30 sec.

Above 13.0V for 90 sec.

Above 27.0V for 30 sec.

Above 26.0V for 90 sec.

Automatically isolates battery

banks when sensed voltage

levels are:

Below 9.6V (undervoltage lockout)

Below 12.35V for 10 sec.

Below 12.75V for 30 sec.

Above 16.2V (overvoltage lockout)

Below 19.2V (undervoltage lockout)

Below 24.7V for 10 sec.

Below 25.5V for 30 sec.

Above 32.4V (overvoltage lockout)

Start Isolation or Engine Isolation.

The isolation inputs enable one of two functions depending on

how the inputs are configured.

NOTE: The ML-Series ACR can be configured for Start Isolation or Engine Isolation, but not both.

Start Isolation - Temporary isolation (3−5 minutes) of house loads from the engine circuit during engine

cranking to protect sensitive electronics. Configure Start Isolation when there are heavy cranking loads

causing sags and spikes that might damage electronics in the House circuit. See page 3.

Engine Isolation - Isolate two engines while both are running to protect engine electronics, and to

maximize alternator output. Configure Engine Isolation when the engine manufacturer requires it, and

when there are separate batteries for each engine. See page 3.

Undervoltage or Overvoltage Lockout.

• Undervoltage lockout prevents batteries from being combined when either battery is below 9.6V@12V DC

operation or 19.2V@24V DC operation.

• Overvoltage lockout prevents batteries from being combined when either battery is above 16.2V@12V DC

operation or 32.4V@24V DC operation.

Control Switch Remote Operation.

Included Contura Control Switch—sustained (SPDT) ON-OFF-ON.

The Control Switch should be mounted in a convenient location near helm controls to allow for quick access.

NOTE: Alternatively use a momentary (SPDT) (ON)-OFF-(ON) or momentary push button switch to provide cross connect and/or battery isolation.

To cross connect

(combine) battery banks

Switch to “ON” combines battery banks to provide more battery power in hard

starting situations.

To isolate battery banks

Switch to “OFF”- when the battery banks are isolated using the Control

Switch, the battery banks remain isolated, and for at least 30 seconds after

the control switch is returned to the “AUTO” position.

Control Switch Remote Indication or ML-ACR Status

NOTE: The remote switch has two LEDs (top and bottom). These LEDs operate simultaneously-either they are both ON or both OFF.

page 1 of 4

PN

Termination

Manual

Control

Control

Circuit

7620

Tinned Wires

No

12V DC

7621

Tinned Wires

No

24V DC

PN

Termination

Manual

Control

Control

Circuit

7622

Tinned Wires

Yes

12V DC

7623

Tinned Wires

Yes

24V DC

LED INDICATION

ACR STATE OR CONDITION

Remote Switch Set to “AUTO” or no Remote Switch Installed
LEDs OFF

Batteries are isolated

LEDs ON

Batteries are combined

LEDs slow steady blink, ON-OFF

Start or Engine Isolation is causing batteries to be isolated

LEDs quick steady blink, ON-OFF

Undervoltage lockout--either battery is below 9.6V@12V DC

operation or 19.2V@24V DC operation.

Overvoltage lockout--either battery is above 16.2V@12V DC

operation or 32.4V@24V DC operation.

Remote Switch Set to OVERRIDE “ON” or “OFF”—Automatic operation is suspended for 10 minutes

after remote switch is returned to “AUTO”
LEDs double blink,

Blink-Blink-Pause, Repeat

Manual override--check ACR for switch states

OR

ACR mechanical failure

Available Models

AWG

Metric (mm²) Cranking 10 sec. Cranking 1 min.

Intermittent Rating 5 min.

Continuous Rating

2/0

70

2,000A

750A

400A

225A

4/0

120

2,200A

750A

400A

300A

2x (4/0)

2x (120)

2,500A

1,100A

700A

500A

Wire Size and Current Ratings