Set initial burner air settings, Prepare burner – Carlin 301CRD User Manual

Page 12

Advertising
background image

Model 201CRD & 301CRD 240-VAC Advanced oil burners — Instruction manual

Carlin part number MN2301A Rev. 10/21/10

– 12 –

Figure 13 Combustion head/air tube combinations, typical

Set initial burner air settings

Combustion head (“A” dimension)

1. The combustion head adjusting screw is used to set the spacing between

the retention ring and throttle ring (or air cone), regulating how much air
passes around the retention ring.

2. See Figure 11.

3. Rotate the head adjusting screw until the distance from the housing detent

to the beginning of the scale equals the value given in Table 4, page 13
(“A” dimension).

Air band

1. See Figure 12. Loosen the air band locking screw and rotate the air band

until the opening equals the percent opening given in Table 4, page 13.

Final adjustments

1. The burner is now adjusted to the approximate air settings for the fi ring

rate chosen.

2. When you check combustion with instruments during start-up or servicing,

you may have to adjust the head and/or air band slightly to achieve the
desired effi ciency.

• Increase the combustion head setting (“A” dimension) to increase air. If

additional adjustment is needed, open the air band slightly.

• Decrease the combustion head setting (“A” dimension) to decrease air. If

additional adjustment is needed, close the air band slightly.

3. See “Adjust burner using test instruments,” page 20.

4. Note that positive pressure overfi re will reduce air fl ow, requiring more air

opening.

Figure 11 Combustion head setting

Figure 12

Air band setting