Prepare burner, Install head positioning bar, Adjust air band (initial setting) – Carlin EZ-1/2/3 User Manual

Page 11

Advertising
background image

Carlin part number MNEZ123 Rev. 07/13/11

– 11 –

Model EZ-1/2/3 oil burners — Instruction manual

3. Prepare burner

(continued)

4. Replace the retention ring assembly by slipping one of the riveted arms

through the gap between the electrode tips. Align this arm straight up,
with the ring clamp firmly against the nozzle adapter shoulder. Then
tighten the clamping screw.

5. Check the electrode settings. Position the electrodes as shown in Fig-

ure 7. These settings are critical in ensuring a reliable ignition. Once
the electrodes are set, check all clamps to be sure they are securely
tightened.

Figure 8 Carefully support the nozzle adapter when

removing or installing nozzle

Install head positioning bar

1. The burner is supplied with up to seven calibrated bars that properly

position the head in the air tube. See the table below for head position-

ing bars available.

2. The head positioning bars are stamped with a nozzle size range. Use a

positioning bar with the range that includes the nozzle size installed.

3. See Figure 9. Remove the existing bar (if installed) and replace with

the correct one.

4. Store any remaining bars in the rear of the burner to allow future

change, if needed.

Model

Range

Head positioning bars available

EZ-1

EZ-1-HP

0.50 – 1.65

GPH

7 options:

0.50 / 0.60-0.65 / 0.75

0.85-1.00 / 1.10-1.25 /

1.10-1.25 / 1.35-1.50 / 1.65

EZ-2

EZ-2-HP

1.50 – 2.25

GPH

4 options:

1.50 / 1.65-1.75

2.00 / 2.25

EZ-3

EZ-3-HP

2.00 – 2.50

GPH

3 options:

2.00 / 2.25 / 2.50

Adjust air band (initial setting)

1. The burner pump pressure is factory set. The pump pressure is indi-

cated on a label affixed to the pump only if it is something other than

100 psi. The air band divisions match the nozzle size regardless of the

pump pressure setting. Loosen the lock screw and move the air band

until the pointers line up with the setting indicated in the OEM Set-up

Table or to a setting that matches the nozzle size (for a retrofit burner).

See figure 10.

2. NOTE: For high altitude installations above 2,000 feet, increase the

air supply setting 4% for each 1,000 feet above 2,000 feet above sea

level.

3. The burner is now adjusted to the approximate air band setting for the

nozzle size indicated. When you check combustion with instruments

during start-up or servicing, you may have to adjust the air band slightly

to achieve the desired combustion readings. See “Adjust burner using
test instruments,” page 22.

Figure 9 Installing head positioning bar

Remove head bar

retaining screw and

disconnect oil line and

knurled nut from nozzle

line.

Install the head bar

with the correct firing

nozzle size range for

the application.

Figure 10 Initial setting of air band

Initially set air band so the

pointer points at the burner

nozzle size.

Advertising