Double piggyback application, Float tree assembly (continued), Simplex control panel applications – Clarus Environmental Turbine STEP Systems User Manual

Page 5: Fig. 6, Fig. 7

Advertising
background image

5

30.5" MAX.

2.5" MIN.

PUMP OFF

PUMP ON

DOUBLE PIGGY BACK

3.5" MIN.

(1" ADDED FOR SAFETY)

SEPTIC TANK MIN. INLET HEIGHT 29"

TOP OF FLOAT TREE

NYLON CABLE TIE

TOP OF FILTER HOLDER

Double Piggyback Application

If using the double piggyback float switch option, the floats should be

set as follows (see Fig. 6).

Clarus Environmental recommends an auxiliary high water alarm

when using the double piggyback float switch option. The alarm

should be plugged into a different circuit than the pump circuit. Follow

the installation instructions provided with the alarm (see Fig. 7).

The alarm must be activated at or before the point when the effluent

level reaches the bottom of the inlet pipe.

Record the actual settings measured from the top of the float tree in

the table provided for future reference.

Fig. 6

Float switch distance from top of the float tree w/o alarm.

Pump on - Gray (below the bottom of the inlet.)

Pump off - Black (maximum 30½")

Float switch distance from top of the float tree with alarm.

Alarm - Black (below or even w/ bottom of inlet)

Pump on - Gray (varies)

Pump off - Black (maximum 30½")

Transferring float locations if the pump vault is hung from the top

of the tank:

When the pump vault is hung, the top of the float tree is 3½" below the

top of the septic tank. Therefore, any distance measured from the top

of the septic tank, minus 3½", will transfer to the top of the float tree

(see Fig. 4 for example).

SK2434G

Float Tree Assembly (continued)

30.5" MAX.

2.5" MIN.

2.5" MIN.

PUMP OFF

PUMP ON

HIGH WATER ALARM

SIMPLEX

3.5" MIN.

(1" ADDED FOR SAFETY)

SEPTIC TANK MIN. INLET HEIGHT 31.5"

TOP OF FILTER HOLDER

TOP OF FLOAT TREE

NYLON CABLE TIE

Fig. 7

SK2434D

If using a simplex control panel, the floats should be set as follows

(see Fig. 7).

The alarm must be activated at or before the point when the effluent

level reaches the bottom of the inlet pipe.

Record the actual settings measured from the top of the float tree in

the table provided for future reference.

Float switch distance from top of the float tree.

Alarm - Black (below or even w/ bottom of inlet)

Pump on - Black (varies)

Pump off - Black (maximum 30½")

Simplex Control Panel Applications

Transferring float locations if the pump vault is placed on the

septic tank floor:

When the pump vault is placed on the floor, the top of the float tree is

52½" from the floor. Measure the depth of the tank and record above.

Subtract any distance measured from the depth of the tank, then sub-

tract that number from 52½" and the answer will transfer to the top of

the float tree (see Fig. 5 for example).