Watertight junction box wiring, Startup – Clarus Environmental Turbine STEP Systems User Manual

Page 8

Advertising
background image

8

Watertight Junction Box Wiring

The preferred location of the junction box is inside the riser. Some

codes require the junction box to be outside the riser. Check with your

local health department and electrical inspector before deciding upon

the location.

• Junction boxes must be watertight. All wiring that passes through

the wall of the box must use watertight connectors and be sealed

properly.

• NOTE: See CL0625B for a list of suggested junction boxes and

CL0620B for prewired conduit assemblies. Junction boxes for the

high head filter system are fully assembled and are provided with a

3/4” PVC conduit attachment and the appropriate number of cord

seals for the pump and floats.

• For junction boxes that are not fully assembled or predrilled, drill

a 1-1/8” hole in the box for the 3/4” PVC conduit fitting. Install with

washer on the outside of box. Silicone is recommended around the

opening for the best seal. Drill a 7/8” hole in the box for each cord

seal. Install with washer on the outside of box. Silicone is recom-

mended around each opening for the best seal.

Startup

Before placing the equipment into operation the following must be

checked:

• Septic tank or pump chamber should be pumped and cleaned prior

to installation in existing system.

• Septic tank or pump chamber must be watertight.

• Installation needs to be according to instructions.

• Installation should include an easy access riser and tamper

resistant lid.

• Filter assembly needs to be in place and secure.

• Float tree needs to be in place, secure and adjusted for

proper cycling.

• Make sure float switches are free to move within the basin.

• Be sure electrical connections are watertight and

conform to the Uniform Building Code and the National Electrical

Code (NEC).

• Fill the septic tank with water and check the system for operation.

After installing the pump into the containment area with adequate

submergence, open the discharge valve fully. Start the unit using manual

controls. If flow is appreciably less than rated performance, pump may

be air locked. To expel trapped air, jog the unit several times, using

the manual controls. If your system has a check valve, make sure the

weep hole is clear.

Check float levels during operation and adjust accordingly as

needed.

Have a qualified electrician take voltage and current measurements

on the black wire of single phase. Record these readings in the space

provided in the “Owner’s Information” section on the front this manual

for future reference.

Be sure to complete all items such as installing the lid on the riser,

securely closing the control panel, and checking the system operation

have been completed before placing the system into service.

© Copyright 2011. All rights reserved.

Advertising