CERTIFICATIoN AND FAILURE RATE DATA
All Safety-Certified FlexSonic Acoustic Detectors are

certified compliant to:
IEC61508: 2010
Type B Element
Systematic Capability: SIL 2 certified
HFT: 0
Low Demand Mode
PFDavg should be calculated for any safety instrumented

function using the FlexSonic Acoustic Detector. (Refer

to FMEDA report for necessary information, including

DU rate.)
Safety Accuracy:

±10% of applied acoustic leak

pressure.

Safety Response Time: Refer to the FlexSonic

Acoustic Detector instruction

manual for details.

Product Life:

10 years, based on

manufacturer data.

All failure rate data for SIL verification is in the FMEDA

report, which is available upon request.

ADDITIoNAL CERTIFICATIoNS
FM, CSA, ATEX, IECEx, CE, and others.

Refer to the FlexSonic Acoustic Detector Instruction

Manual for details.

For complete information regarding performance,

installation, operation, maintenance and specifications

of the FlexSonic Acoustic Detector, refer to instruction

manual 95-8657.

TERMS AND DEFINITIoNS

AMS

Asset Management System

FMEDA

Failure Mode Effects and Diagnostics

Analysis

HART

Highway Addressable Remote

Transducer

HFT

Hardware Fault Tolerance

PFD

Probability of Failure on Demand

(Probability of Dangerous Failure)

PFDavg

Average Probability of Failure on

Demand

SFF

Safe Failure Fraction

SIF

Safety Instrumented Function

SIL

Safety Integrity Level

SIS

Safety Instrumented System

AC100

Acoustic Sensor (contains microphone,

AIC acoustic source, and associated

circuitry)

ATX10

Transmitter for acoustic spectrum

analysis and control functions

Acoustic

Detector

Consists of one Model AC100 Sensor

and one Model ATX10 Transmitter

UD10 FlexVu

®

Model UD10 Universal Display

Detector Electronics Corporation

6901 West 110th Street • Minneapolis, Minnesota 55438 USA

Operator: (952) 941-5665 or (800) 765-FIRE

Customer Service: (952) 946-6491 • Fax (952) 829-8750

http://www.det-tronics.com • E-mail: [email protected]

Specifications subject to change without notice.

Det-Tronics and FlexSonic are registered trademarks or trademarks of
Detector Electronics Corporation in the United States, other countries, or both.
Other company, product, or service names may be trademarks or service
marks of others.

©Copyright Detector Electronics Corporation 2013. All rights reserved.

R

EG

IST

ERE

D BY UL AN

D B

SI

NO

. A2305 • NO. 2582

6

ISO 9001

RE

GIS

TERED FIRM

R

EG

IS

TERED FIR

M

Failure Category

l

sd

l

su

2

l

dd

l

du

SFF

3

Acoustic Detector Analog Output (consists of one Model

AC100 Sensor and one Model ATX10 Transmitter)

0

125

1925

97

95.5

IEC 61508 Failure Rates in FIT

1

1

FIT = 1 Failure / 10

9

Hours

2

It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to IEC 61508,
ed2, 2010.

3

Safe Failure Fraction needs to be calculated on (sub)system level.